2.8 Installation location
The Device can be installed either on a table or a 19-inch cabinet rack.
(1) Table
Install the Device on a level, stable and flat table. When installing the Device on a desktop,
consider the requirements described in the following table.
Table 2-5 Conditions for installing the device on a table
Item
Conditions
Space for air intake
and exhaust
Ensure at least 70 mm of space around all air vents of the Device. (For details, see
2.10 Cooling requirements.)
Space for cables
Ensure 100 mm of space in front of the Device and 50 mm of space behind the
Device for the routing of cables.
#1
Noise of the device
For details about noise, see 2.11 Device Noise.
#1: When using the Device in a 200 V AC environment, ensure 100 mm of space behind
the Device.
If placing the Device on a desk, lay it on its side on a workbench capable of
withstanding the weight of the device. Placing the Device in an unstable location, such
as on an unsteady or tilting surface, might cause the device to fall, resulting in serious
injury to yourself and others.
(2) 19-inch cabinet rack
When mounting the Device on a rack, be sure to satisfy the rack requirements described in
Table 2-6 Rack requirements.
In addition, prepare the brackets described in Table 2-7 Required brackets and the screws
described in Table 2-8 Number of required screws.
Table 2-6 Rack requirements
Item
Conditions
Rack standard
19-inch cabinet rack conforming to the EIA standard
#1
Space for air intake
and exhaust
Ensure 70 mm or more of space between all air vents of the Device and the rack
pillars and side walls. (For details, see 2.10 Cooling conditions.)
Space for cables
Ensure 100 mm of space in front of the Device and 50 mm of space behind the
Device for the routing of cables.
#2 #3
#1: A rack fixture attached to a Device supports a 19-inch cabinet rack conforming to the
EIA standard.
To use a 19-inch cabinet rack conforming to the JIS standard, contact your sales
representative.
#2: When using the Device in a 200 V AC environment, ensure 100 mm of space behind
the Device.
Содержание GX1000-SMC013X
Страница 94: ...94 5 Configuration Guide 5 1 Base Software Configuration Guide ...
Страница 105: ...105 7 Access Lists 7 1 Access lists ...
Страница 153: ...153 8 Policy Based Switching 8 1 Policy based switching ...
Страница 165: ...165 9 Policy Based Routing 9 1 Policy based routing ...
Страница 177: ...177 Figure 10 1 Overview of mode transitions ...
Страница 188: ...188 14 Configuration Command Reference 14 1 Reading the configuration command reference 14 2 SNMP 14 3 SP functionality ...
Страница 208: ...208 16 Message and Log Reference 16 1 Operation messages and logs 16 2 Device Failure and Event Information ...
Страница 213: ...213 17 MIB Reference 17 1 Private MIBs 17 2 Supported MIB Traps ...
Страница 224: ...224 19 1 Starting the device For details see 5 1 Login procedures in the Base Software Configuration Guide ...
Страница 229: ...229 H W BOOT 11 44 MISC 1 0 SPCT 0 34 10 The updating of the SP files is finished ...
Страница 448: ...448 27 Notes This chapter provides notes on using the WAN acceleration functionality 27 1 Note ...
Страница 451: ...451 28 Additional Information ...