78
[33] Outdoor EEPROM failure
[34] Protection of discharging temp. too high
If sensor terminal is fixed well
If sensor resistor/characteristic
is proper
If the system is lack of
refrigerant
If the EEPROM is fixed well
Replace connecting board
Replace EEPROM
Reconnect
Replace sensor
Charge refrigerant
Reconnect
Y
Y
N
Y
N
N
Y
N