4
4. Description Of Main Components
Structure
Panels and base are made from galvanized steel plate painted with epoxy power to ensure total resistance to
atmospheric pollution, condensate collection pan as standard.
Air cooled coils:
The coils are made from high performance and seamless copper tuber and high surface area aluminum fins to
ensure optimum heat exchange capability. Condenser coil protection grill is standard.
Fan motor:
To achieve high efficiency heat exchange, the unit is equipment with the high performance axial-flow fans. The fan
is driven directly by weather proof motor to ensure reliable operation, the fan motor is six-pole electric motor with
built-in thermal cut-out.
Hydraulic module:
It is fully integrated and equipped with key hydraulic components such as Coaxial heat exchanger (applied for
AU082) and tubes in shell heater exchanger (applied for AU112/162). water circulating pump.The water pressure
difference switch is provided in the units to protect against damage to the water pump.
Power and control electrical panel
Power and control electrical panel constructed in accordance with IEC 204-1/EN60335-2-40, complete with
compressor contactor,control via control panel.
1.Compressor 2.Coaxial heat exchanger
3.Electrical panel 4.Condenser
5.Motor bracket 6.Axial-flow fan
7.Motor 8.Water Pump
9.Pressure Difference switch 10.Safety valve
11.4-ways valve 12.Solenoid valve
13.Electronic expansion valve 14.High pressure switch
15.Low pressure sensor 16.High pressure sensor
AU082FYCRA (HW)
Содержание AU082FYCRA(HW)
Страница 1: ...ATW Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Страница 11: ...9 405 410 600 174 174 450 950 965 395 6 Dimensions AU082FYCRA HW Unit mm ...
Страница 12: ...10 AU112 162FYCRA HW Unit mm 1490 950 380 187 405 410 600 174 174 450 170 ...
Страница 13: ...11 AU082FYCRA HW 7 Piping Diagram ...
Страница 14: ...12 AU112 162FYCRA HW ...
Страница 27: ...25 12 Water Pressure Drop ...
Страница 28: ...26 ...
Страница 57: ...55 15 PCB Photo BM2 BM1 PCB code 0151800423 ...