57
17. Digital Tube Display
SW1 SW2 SW3
Segment digital tube display content LD2~4
0
0
0 Err code: “000” means no err happen
0
2
0
Operating mode: Stop:OFF; Cooling mode: CCC; Heating mode: HHH;
0
3
0 Outdoor fan 1 motor speed(rpm) “345” means 345rpm.
•Motor speed can be set through pressing “ENTER(SW7)”
with 3 seconds, in which “111” will be displayed and the speed
and speed class will be showed in turn. Speed class can be
increased a grade through pressing “UP”once and can be
decreased a grade through pressing “DOWN”once;
•“000” will be showed through pressing “Exit(SW6)” with 3
seconds and setting mode will be exit.
0
4
0 Outdoor fan 2 motor speed(rpm)
Main function instruction:
By setting the rotary switch, the digital tube will display the unit parameters, the data is inform
of decimal integer. During the process of installation, adjustion and maintenance, the whole
system’s operating parameters can be tested conveniently which can help to check and solve
problems quickly and correctly.
SW1
SW2
SW3
Содержание AU082FYCRA(HW)
Страница 1: ...ATW Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Страница 11: ...9 405 410 600 174 174 450 950 965 395 6 Dimensions AU082FYCRA HW Unit mm ...
Страница 12: ...10 AU112 162FYCRA HW Unit mm 1490 950 380 187 405 410 600 174 174 450 170 ...
Страница 13: ...11 AU082FYCRA HW 7 Piping Diagram ...
Страница 14: ...12 AU112 162FYCRA HW ...
Страница 27: ...25 12 Water Pressure Drop ...
Страница 28: ...26 ...
Страница 57: ...55 15 PCB Photo BM2 BM1 PCB code 0151800423 ...