[71-0,71-1 ] DC motor blocked
Replace fan motor
Rotate fan motor by hand to
check if there is obviously fiction
Check the motor and PCB
connection is well
Forced the fan in low speed,
measure if it has alternating
voltage between FG and GND
Replace the
outdoor PCB
Re-connect
Replace the motor
Y
N
Y
Y
N
N