BM1 introduction
BM2 introduction
BM1_1
Control type selection
OFF Wired controller control (default)
ON IO board control
BM1_2
BM1_3
BM1_4
BM1_5
Outdoor unit Model selection
[2] [3]
[4]
[5] Outdoor unit Model selection
OFF OFF ON OFF AU082FYCRA(HW)
OFF ON OFF OFF AU112FYCRA(HW)
OFF ON OFF ON AU162FYCRA(HW)
BM1_6
Power selection
OFF Single phase (default)
ON Three phases
BM1_7
Reserved
OFF Reserved (default)
ON Reserved
BM1_8
IO board selection
OFF No IO board (default)
ON Connect with IO board
BM2_1
Heat exchange unit type
OFF
Air condition heat exchange unit(default)
ON
Hot water heat exchange unit
BM2_2
Control mode selection
OFF
Networking (default)
ON
2-way valve linkage
BM2_3
HU electrical heating control mode
OFF
HU electrical heating auto control (default)
ON
HU electrical heating force close
BM2_4
Water flow switch fault shielding
selection
OFF
Normal detection (default)
ON
Shield for a short time, then resume normal
detection
BM2_5
PC and MODBUS selection
OFF
PC monitor (default)
ON
MODBUS
BM2_6
BM2_7
Running mode selection
[6]
[7] Running mode selection
OFF OFF Normal mode (default)
OFF
ON Powerful mode
ON
OFF Silent mode
BM2_8
Hot water mode selection
OFF
No hot water (default)
ON
Hot water mode
bridge instruction
CJ1:
Short it before power ON-- PCB check its function (used for factory production. Short it after power ON-- time short
function, 60 seconds become to 1 second. CJ2: Reserved
16. Dip Switch Setting
Содержание AU082FYCRA(HW)
Страница 1: ...ATW Service Manual SYJS 03 2019REV A Edition 2019 03 ...
Страница 11: ...9 405 410 600 174 174 450 950 965 395 6 Dimensions AU082FYCRA HW Unit mm ...
Страница 12: ...10 AU112 162FYCRA HW Unit mm 1490 950 380 187 405 410 600 174 174 450 170 ...
Страница 13: ...11 AU082FYCRA HW 7 Piping Diagram ...
Страница 14: ...12 AU112 162FYCRA HW ...
Страница 27: ...25 12 Water Pressure Drop ...
Страница 28: ...26 ...
Страница 57: ...55 15 PCB Photo BM2 BM1 PCB code 0151800423 ...