11. Operation Limits Delivery-Leaving
a)Ethylene Glycol Solutions
Water and ethylene glycol solutions used as a thermal vector in the place of water reduce the performance of the
unit. Multiply the performance figures by the values given in the following table.
cPf:
correction factor of heating/cooling capacity
cQ:
correction factor of flow rate
cdp:
correction factor of pressure drop
Freezing point ( C)
0
-5
-10
-15
-20
-25
Percentage of ethylene glycol in weight
0
12%
20%
28%
35%
40%
cPf
1
0.98
0.97
0.965
0.96
0.955
cQ
1
1.02
1.04
1.075
1.11
1.14
cdp
1
1.07
1.11
1.18
1.22
1.24