(2)Installation and maintenance space
Selection of installation location of outdoor
(1)Single-unit installation (unit: in.(mm))
The top and two side surfaces must be exposed to open space, and barriers on at least one side of the front and
back shall be lower than the outdoor unit.
(2)Multi-unit installation (unit: in.(mm))
(3)Multi-unit installation in front and back (unit: in.(mm))
The top and two side surfaces must be exposed
to open space, and barriers on at least one side
of the front and back shall be lower than the
outdoor unit.
•
The installation service spaces shown in the illustrations are based on an air intake temperature of 95°F(35°C)(DB)
for COOL operation. In regions where the air intake temperature regularly exceeds 95°F(35°C)(DB), or if the heat
load of outdoor units is expected to regularly exceed the maximum operating capacity, reserve a larger space than
that indicated at the air intake side of units.
•Regarding the required air outlet space, position the units with consideration to the space required for the onsite
refrigerant piping work as well. Consult your dealer if the work conditions do not match those in the drawings.