GVS K-BUS
○
R
KNX/EIB
Thermostat
www.video-star.com.cn
Tel.
:
(
8620
)
39338986
Fax.
:(
8620
)
39338465
67
1BYTE
If this parameter is visible when "function switchover blinds/roller shutter" selects "shutter", and is
used to set the object types of "Output shutter UP/DOWN" and "Output Stop/lamella adj".
Parameter “Cyclical transmission tele. repetition (Entry*0.1s)"
Options: 3-250
The parameter is visible when selecting"1bit" in the parameter "object type", where setting the
switch's long press operation, the interval of two telegrams is sent cyclically.
Parameter “value for position down (%)”/“value for position up (%)”
This parameter can only be set if “1 byte” has been set as object type, which can be used to set the
position (percent values) that a connected blind shall be lowered or raised to. Options: 0~100, the value
0% means travel up completely, the value 100% means travel down completely.
Parameter “value for stats position down (%)”/“value for stats position up (%)”
This parameter can only be set if “1 byte” has been set as object type, which can be used to set the
position (percent values) that a connected blind slat shall be opened or closed to. Options: 0~100, the
value 0% means slat opened completely, the value 100% means closed completely.
4.12.4
Scene
In "Input 1/2/3", when selecting "Scene" for "Function of input 1 /2/3", the parameter window is seen
as Figure 4.12.5: if this function is enabled, sending and saving the scene can be achieved.