GVS K-BUS
○
R
KNX/EIB
Thermostat
www.video-star.com.cn
Tel.
:
(
8620
)
39338986
Fax.
:(
8620
)
39338465
51
Send following telegram cyclically
These two parameters are used to respectively set ways of sending telegram to the object
"1bit/1byte output, humidity", when the detected humidity is below the low threshold or above the high
threshold.
If select "do not send telegram", the object does not sends telegram;
If select "send following telegram once", the object sends telegram once;
If select "send cyclically", the object sends telegram cyclically, sending time can be set in the
following parameter "cycle time for humidity threshold value [min]" in the settings, you can send two
object types, the value of the object is set in the following parameters "logic1bit / 1byte telegram value ".
Parameter "logic 1 bit /1byte telegram value"
Options: Logic 1bit (0~1)
1byte
(
0~255
)
This parameter is used to specify, the telegram value that object "1bit/1byte output, humidity" sends,
when the current humidity is below the low threshold and above the high threshold.
After a bus reset
or programming, if the current humidity is between the low threshold and the high threshold, the object
does not send telegram to the bus.
Parameter "Cycle time for humidity threshold value [min](if used)"
Options: 1- 255
This parameter is used to set the object "1bit/1byte output, humidity" cycle time on the bus to send
the value of the interval, only when the parameter "If humidity is lower / upper than threshold value" set
loop send it to use.
Parameter "use block of the humidity threshold output"
Options: yes
no
This parameter sets whether to enable the threshold value, if enabled, the object "humidity
threshold value1 / 2 block" is visible, when the object receives telegram "1", threshold value is disabled,
when the object receives telegram "0", the threshold value is enabled.