"1bit/1byte output, temperature", when the detected temperature is below the low threshold or above the
high threshold.
If select "do not send telegram", no telegram is sent; if select "send following telegram once", the
telegram is sent once; if select "send cyclically", the telegram is sent cyclically; send cyclically time can
be set in the below "cycle time for temperature threshold value [min]", and at most two values can be set,
in the below logic1bit/ 1byte telegram value.
Parameter "logic 1 bit /1byte telegram value"
Options: Logic 1bit (0~1)
1byte
(
0~255
)
This parameter is used to specify, the telegram value that object "1bit/1byte output, temperature"
sends, when the current temperature is below the low threshold and above the high threshold. After a
bus reset or programming, if the current temperature is between the low threshold and the high threshold,
the object does not send telegram to the bus.
Parameter "Cycle time for temperature threshold value [min](if used)"
Options: 1- 255
This parameter is used to set the object "1bit/1byte output, temperature" cycle time on the bus to
send the value of the interval, only when the parameter "If temperature is lower / upper than threshold
value" set loop send it to use.
Parameter "use block of the temperature threshold output"
Options: yes
no
This parameter sets whether to enable the threshold value, if enabled, the object "temperature
threshold value1 / 2 block" is visible, when the object receives telegram "1", threshold value is disabled,
when the object receives telegram "0", the threshold value is enabled.
Parameter "Behaviour when setting the lock"
Options: Do not send telegram
Send the same telegram as lower threshold