GVS K-BUS
○
R
KNX/EIB
Thermostat
www.video-star.com.cn
Tel.
:
(
8620
)
39338986
Fax.
:(
8620
)
39338465
83
35/39
Change humidity threshold
value 1/2
Humidity threshold value 1/2
2byte
C, R,W
9.007
DPT_Value_Humidity
This communication object is used to change the humidity's high threshold value; telegram range: 0…100%
36/40
1 bit output humidity
Humidity threshold value 1/2
1bit
C, R,T
1.001 DPT_Switch
When the humidity is higher than the current high threshold or below the low threshold, 1bit telegram can be sent via this
object to the bus, specific telegrams can be set by the parameter "logic 1bit telegram value [0 ... 1]".
37/41
1 byte output humidity
Humidity threshold value 1/2
1byte
C, R,T
5.010
DPT_Value_1_Ucount
When the humidity is higher than the current high threshold or below the low threshold, 1bit telegram can be sent via this object
to the bus, specific telegrams can be set by the parameter "1byte telegram value[0…255]".
38/42
Humidity threshold value 1/2
block
Humidity threshold value 1/2
1bit
C,R,W
1.001 DPT_Switch
This communication object is used to disable or enable the function of the humidity threshold value. Disabled and enabled
actions can be set by the parameter.
Receive telegram "1" - disable the humidity threshold value
Receive telegram "0" - enable the humidity threshold value
5.4 "Logic" Communication Object
Figure 5.4 Logic communication object
Number
Object name
Functions
Data Types
Flags
DPT
43
Logic input A
Logic input
1bit
C, R,W
1.001 DPT_Switch
This communication object is used to receive the value of logic Input A.
44
Logic input B
Logic input
1bit
C, R,W
1.001 DPT_Switch
This communication object is used to receive the value of logic Input B.
45/48
Logic 1/2, 1 bit output
Logic 1/2
1bit
C, R,T
1.001 DPT_Switch