by multiple sensors, or temperature by external sensor.
4
rel. humidity
Humidity
2 byte
C, R, T
9.007 DPT_Value_Humidity
The communication object is used to send the current humidity that is detected by the thermostat panel sensor, to the
bus; the transmission time is set via parameter settings.
5
Operating mode forced object
Setpoint
temperature
1 byte
C,R,W
20.102 DPT_HVACMode
This communication object is mandatory conversion of operating mode, and has the highest priority. Different
telegrams mean different operating modes, as follows: 0: Auto (comfortable), 1: comfort mode, 2: Standby mode, 3: Night
Mode, 4: Frozen protection /heat protection, 5~255: Reserved, do not use. For example, when an object receives a
telegram "2", the thermostat panel will control the actuator according to the standby mode setting.
6
Window status
Setpoint
temperature
1 bit
C, R, W
1.019 DPT_Window_Door
This communication object is used to connect a window contact
Receive telegram "1" - the windows open
Receive telegram "0" - the windows closed
7
Presence object:
Setpoint
temperature
1 bit
C, R,W
1.001 DPT_Switch
This communication object is used to connect presence sensor
Receive telegram "1" - somebody or something exists
Receive telegram "0" - somebody or something doesn't exist
8
Active comfort mode
Setpoint
temperature
1 bit
C, R,W
1.001 DPT_Switch
The communication object is visible when the object type of operating mode is "1bit", and is used to activate comfort
mode. Receiving telegram "1"will activate comfort mode; receiving telegram "0" will not activate comfort mode.
Receive telegram "1"----activate comfort mode
Receive telegram "0"----not activate comfort mode
9
Active standby mode
Setpoint
temperature
1 bit
C, R,W
1.001 DPT_Switch