background image

Printed in U.S.A.

9/08

©

 

Copyright 2008 TAC All Rights Reserved.

F-11302-9

Application

For line voltage on-off control of media temperatures in ducts, 
tanks, liquid lines, pipes, etc.

Specifications

Setpoint Dial Range: See Tables 1 and 2.
Sensing Element: Helical bimetal.
Differential: See Tables 1 and 2.
Shipping Ambient Temperature Limits: -40 to 160°F (-40 
to 71°C).
Electrical Switch: See Tables 1 and 2.
Connections: Coded terminals.
Cover: Beige painted steel case with 1/2" conduit opening.
Locations: NEMA Type 1 indoor only.
Mounting: In any position on any surface not subject to 
excessive vibration. For immersion mounting AT-223 will is 
required. Extension mounting bracket (provided) is required 
by UL for duct installation of TA-3434 and TC-3413.
Dimensions:

Case, 5-3/8" high x 3-1/2" wide x 1-7/8" deep (136 mm x 
89 mm x 48 mm).
Element, 1/2" diameter x 7-1/2" insertion length, overall 
length 9-3/8" (131 mm x 191 mm x 238 mm).

ACCESSORIES
AT-223 

Brass bulb well (see below)

Table-1 Specifications.

Part 

Number

Device Type

Functional 

Setpoint Dial 

Range

°F (°C)

a

a

Units dual marked °F and °C.

Sensor 

Ambient 

°F (°C)

Differential 

°F (°C)

Switch Type

Voltage

Full 

Load 

Amps

Locked 

Rotor 

Amps 

Pilot 
Duty 

(VA)

Min.

Max.

TA-3432

High temp. 

manual reset

75 to 135 (23 

to 57)

-25 

(-32)

235 

(113)

Fixed 

b

10 (5)

SPST opens on 

temp. rise

120

16

96

720

240

8

48

TA-3433

High temp. 

manual reset

100 to 160 

(38 to 71)

(-18)

260 

(127)

Fixed 

b

5 (3)

SPST opens on 

temp. rise

120

16

96

720

240

8

48

TA-3434

High temp. 

manual reset

120 to 240 

(49 to 116)

20

 (-7)

300 

(149)

Fixed 

b

10 (5)

b

Reset cannot be accomplished until the sensed temperature is at least 5°F (3°C) below setpoint.

SPST opens on 

temp. rise

120

16

96

720

240

8

48

TA-3441

Low temp. 

manual reset

35 to 59 (1.7 

to 15)

-40 

(-40)

159 

(71)

Fixed 

c

10 (5)

c

Reset cannot be accomplished until the sensed temperature is at least 5°F (3°C) above setpoint.

SPST opens on 

temp. drop

120

16

96

720

240

8

48

TA-3432, TA-3433, TA-3434,

TA-3441, TC-3411, TC-3413

Duct and Immersion Electric Thermostats

General Instructions

Figure-1 Switch Action and Terminal Identification.

Отзывы: