4.9.2 Humidity threshold value
Figure 4.9.2 Parameter window "Humidity threshold value 1/2"
Parameter "Humidity threshold value (%)"
Options: 0- 100
This parameter sets a high threshold value humidity, this threshold value can be changed as
"change humidity threshold value1 / 2", and once changing, in the bus will save the new value when the
power of the BUS is off.
Parameter "Negative hysteresis humidity (%)"
Options: 1-10
This parameter is used to set the hysteresis value of the low threshold value to high threshold value.
Assuming the hysteresis value is 5%, then the lower threshold = high threshold value -5%. When
the high threshold changes, the low threshold changes accordingly.
Parameter "If humidity is lower than threshold value"
Parameter "If humidity is upper than threshold value"
Options: Do not send telegram
Send following telegram once