Overhead Ceiling Fans
4
®
UNISTRUT COMPONENTS
(BY OTHERS)
UNISTRUT INSTALLATION
MANUAL PAGE 21
FASTENERS PROVIDED BY OTHERS
IMPORTANT:
UNISTRUT MUST BE MINIMUM OF
1-5/8 x 1-5/8 IN. STEEL WITH 12 GAUGE THICKNESS
IMPORTANT:
SPAN LENGTH MUST NOT
EXCEED 8 FT.
IMPORTANT:
DO NOT HANG OR SUSPEND
UNISTRUT FROM STRUCTURE. UNISTRUT MUST
REST ON TOP OF STRUCTURE AND BE DIRECTLY
FASTENED TO STRUCTURE WITH THREADED
CONNECTION. USE LOCKTITE ON FASTENERS.
Z-PURLIN
(BY OTHERS)
1/2 in. - 13 x 1.75 GRADE 8 BOLT
Z-PURLIN BACKING PLATE
Z-PURLIN BRACKET
1/2 in. - 13 x 1.75 GRADE 8 BOLT
1/2 in. WASHER
1/2 in. - 13 x 1.75 GRADE 8 BOLT
1/2 in. - 13 GRADE 8 NYLON LOCKNUT
1/2 in. WASHER
1/2 in. - 13 GRADE 8
NYLON LOCKNUT
1/2 in. WASHER
1/2 in. - 13 GRADE 8 NYLON LOCKNUT
DOWNTUBE & MOUNT ASSEMBLY
Z-PURLIN
(BY OTHERS)
STRUCTURAL STEEL ANGLES
(BY OTHERS)
Z-PURLIN INSTALLATION
MANUAL PAGE 20
FASTENER KIT 915431
IMPORTANT:
Z-PURLINS MUST HAVE
MINIMUM 2 IN. FLANGE WITH 12
GAUGE THICKNESS
IMPORTANT:
STEEL ANGLES MUST
BE MINIMUM OF 4 x 4 x 1/4 IN. THICK
IMPORTANT:
SPAN LENGTH MUST
NOT EXCEED 8 FT.
IMPORTANT:
TORQUE ALL BOLTS TO 80 FT-LBF (108.5 N-m)
IMPORTANT:
TORQUE ALL BOLTS TO 80 FT-LBF (108.5 N-m)
Refer