Overhead Ceiling Fans
20
®
Z-Purlin Mounting Kit
IMPORTANT:
Structural Engineer of Record (SEOR)
must perform thorough evaluation of mounting structure
and determine final mounting requirements before fan
is installed. Manufacturer is not liable for any problems
that arise as the result of insufficient structure, including
(but not limited to) vibration, noise, or safety hazards.
Product warranty will be voided at manufacturer’s
discretion if structure is deemed insufficient.
Installations must comply with the following
requirements at a minimum, but SEOR may require
more stringent specifications at their discretion:
Do not install HVLS fans on a single z-purlin.
Structural steel angles must be used to span a
minimum of 2 z-purlins.
Z-purlins must have a minimum flange width of
2 inch and a minimum material thickness of 12
gauge steel.
Structural steel angle span lengths must not
exceed 8 feet. For span lengths up to 8 feet, a
minimum of 2 structural steel angles are required.
Size of structural steel angles must be specified by
a structural engineer. Angles must be a minimum
of 4 x 4 x 1/4 inch thick. Larger angles may be
required for span lengths up to 8 feet. Angles shall
be sufficiently stiff to avoid harmonic resonance
excitation during fan operation (120 RPM;
+/- 20%).
Required Loose Components (Included):
• Z-Purlin Backing Plate (2)
• Z-Purlin Mounting Bracket (2)
Required Components from Bag # 915431:
• 1/2 in. – 13 x 1-3/4 in. Grade 8 Hex Bolt (20)
• 1/2 in. – 13 Grade 8 Nylon Locknut (20)
• 1/2 in. Washer (40)
Hardware/Tools Needed (Not Included):
• Structural Steel Angles (2)
• Torque Wrench
• 3/4 in. Socket and Wrench
• 3/4 in. Wrench
• Drill and 9/16 in. Drill Bit
1. Locate desired fan hanging location. Using the
supplied z-purlin mounting brackets as templates,
mark and drill (4) 9/16 in. holes in each z-purlin.
Z-PURLIN
BACKING PLATE
1/2 in. - 13 x 1-3/4 in.
GRADE 8 HEX BOLT
Z-PURLIN
1/2 in. WASHER
Z-PURLIN MOUNTING
BRACKET
1/2 in. - 13 GRADE 8
NYLON LOCKNUT
TORQUE TO 80 FT∙LBF
(108.5 N∙m)
2. Mount z-purlin mounting brackets and backing
plates using supplied (8) 1/2 in. – 13 x 1-3/4 in.
grade 8 hex bolts, (16) 1/2 in. washers, and (8) 1/2
in. – 13 grade 8 nylon locknuts. Torque hardware to
80 ft∙lbf (108.5 N∙m).
3. Size structural steel angles (by others) to fit within
z-purlins and installed z-purlin mounting brackets.
Size of angle to be determined by structural
engineer.
4. Bolt structural steel angles in place using supplied
(8) 1/2 in. – 13 x 1-3/4 in. grade 8 hex bolts, (16)
1/2 in. washers, and (8) 1/2 in. – 13 grade 8 nylon
locknuts. Torque hardware to 80 ft∙lbf (108.5 N∙m).
STRUCTURAL STEEL ANGLES
(BY OTHERS)
1/2 in. - 13 x 1-3/4 in.
GRADE 8 HEX BOLT
Z-PURLIN
1/2 in. WASHER
Z-PURLIN BRACKET
1/2 in. - 13 GRADE 8
NYLON LOCKNUT
TORQUE TO 80 FT∙LBF
(108.5 N∙m)
TORQUE TO 80 FT∙LBF
(108.5 N∙m)
5. Using the universal mounting plate as a template,
mark and drill (4) 9/16 in. holes in structural steel
angles.
6. Align the universal mounting plate and bolt into
place using (4) 1/2 in. – 13 x 1-3/4 in. grade 8 hex
bolts, (8) 1/2 in. washers, and (4) 1/2 in. – 13 grade
8 nylon locknuts. Torque hardware to 80 ft∙lbf
(108.5 N∙m).
STRUCTURAL STEEL ANGLES
(BY OTHERS)
1/2 in. - 13 x 1-3/4 in. GRADE 8 HEX BOLT
DOWNTUBE & MOUNT ASSEMBLY
1/2 in. WASHER
UNIVERSAL MOUNTING PLATE
1/2 in. - 13 GRADE 8 NYLON LOCKNUT
TORQUE TO 80 FT∙LBF
(108.5 N m)
7. Turn to page 22 to continue with Motor/Hub to
Downtube Installation.
Refer
ence
Tr
oubleshooting
Oper
ation And
Maintenance
Fan
Netw
orking
Electrical
Installation
Fir
e System
Integr
ation
Mechanical Installation
Pr
e-Installation
Gener
al
Information
Quick Start
Guide