1. Set dipswitch 2 as shown below. Dipswitch 2 is
used to set parameters that improve network
function and will need to be adjusted for all fans in
the network except for the first fan.
Position 1 – Off
Position 2 – Off
Position 3 – Off
2. Adjust positions 1 – 5 on dipswitch 3 so that each
successive fan has a unique Modbus address. A
table with all possible Modbus addresses is shown
to the right.
IMPORTANT:
Positions 6 - 8 are used to set parameters
needed for fan operation and should not be adjusted.
Default settings are as follows:
Position 6 – On
Position 7 – Off
Position 8 – Off
NOTE:
It is good practice to use successive Modbus
addresses for networked fans, but this is not necessary
for proper functioning of the network.
3. On the low voltage wiring terminal strip, remove
the 24V (white-brown) wire and cap with a wire
nut or heat shrink. When complete, verify that the
low voltage wiring terminal strip on the VFD circuit
board is wired as shown in the diagram and picture
on pages 38-39.
4. Reinstall the black plastic cover that was previously
set aside on the front of the VFD.
Modbus Address Settings - Dipswitch 3
Fan
Number
Modbus
Address
Position
1
Position
2
Position
3
Position
4
Position
5
Position
6, 7, 8
N/A
1
RESERVED FOR HVLS FAN CONTROLS
Do Not
Modify
1
2
On
Off
Off
Off
Off
2
3
Off
On
Off
Off
Off
3
4
On
On
Off
Off
Off
4
5
Off
Off
On
Off
Off
5
6
On
Off
On
Off
Off
6
7
Off
On
On
Off
Off
7
8
On
On
On
Off
Off
8
9
Off
Off
Off
On
Off
9
10
On
Off
Off
On
Off
10
11
Off
On
Off
On
Off
11
12
On
On
Off
On
Off
12
13
Off
Off
On
On
Off
13
14
On
Off
On
On
Off
14
15
Off
On
On
On
Off
15
16
On
On
On
On
Off
16
17
Off
Off
Off
Off
On
17
18
On
Off
Off
Off
On
18
19
Off
On
Off
Off
On
19
20
On
On
Off
Off
On
20
21
Off
Off
On
Off
On
21
22
On
Off
On
Off
On
22
23
Off
On
On
Off
On
23
24
On
On
On
Off
On
24
25
Off
Off
Off
On
On
25
26
On
Off
Off
On
On
26
27
Off
On
Off
On
On
27
28
On
On
Off
On
On
GND
FIRE +
FIRE -
DATA +
DATA -
0-10V
GND
(OPTIONAL)
ALL OTHER FANS IN SERIES
GND
FIRE +
FIRE -
DATA +
DATA -
0-10V
GND
(OPTIONAL)
LOW VOLTAGE WIRING
24v
FIRST FAN IN SERIES
LOW VOLTAGE WIRING
DIP SWITCH BANK 2
1
2
3
4
5
6
7
8
ON
1
2
3
ON
DIP SWITCH BANK 3
DIP SWITCH BANK 2
1
2
3
4
5
6
7
8
ON
1
2
3
ON
DIP SWITCH BANK 3
E
F
Refer
ence
Tr
oubleshooting
Oper
ation And
Maintenance
Fan
Netw
orking
Electrical
Installation
Fir
e System
Integr
ation
Mechanical Installation
Pr
e-Installation
Gener
al
Information
Quick Start
Guide