Fire System Integration (Optional)
The following instructions apply to fans that were
supplied with plug-and-play factory wiring.
DANGER
Always disconnect, lock and tag power source before
installing or servicing. Failure to disconnect power
source can result in fire, shock or serious injury.
DANGER
Pour écarter les risques d’incendie, de choc électrique
ou de blessure grave, veiller à toujours débrancher,
verrouiller et étiqueter la source de courant avant
l’installation ou l’entretien.
NOTE:
The following instructions are only applicable
to buildings that are equipped with a fire suppression
system. If the building does not contain a fire
suppression system, leave the crimp connector on
the fire alarm landing point (located at the top of the
downtube) and continue with the rest of the installation.
IMPORTANT:
HVLS fans must be installed with the
supplied, normally-closed PAM-1 fire alarm relay or an
equivalent electromechanical or reed relay for proper
function of the fire alarm emergency stop feature. Solid
state relays or other digital switching relays cannot be
used.
IMPORTANT:
The fire alarm relay should only be
installed by qualified personnel who are familiar with
the operation of building fire suppression systems. It is
the sole responsibility of the installer to ensure correct
operation of the fire alarm relay in the event of a fire
emergency in the building.
Required Loose Components (Included):
• Low Voltage (24VDC/VAC or 115VAC), Normally
Closed Relay (1)
Hardware/Tools Needed (Not Included):
• Standard Screwdriver
• Cable Cutters
• Wire Strippers
1. If the building is equipped with a fire suppression
system, remove the crimp connector from the fire
alarm emergency stop landing point located at the
top of the downtube by snipping the wires directly
below the crimp connector.
2. Strip the loose wires and wire the supplied
normally-closed relay to the fire alarm emergency
stop landing point and the building’s fire
suppression system using the wiring diagram
shown.
Fire System Integration
SUPPLIED FIRE RELAY
RED (+)
WHITE (-)
YELLOW (NC)
BLUE (COMMON)
BLACK
RED
FIRE ALARM
CONTROL PANEL
RED
WHITE