Overhead Ceiling Fans
19
®
Wood Beam Mounting Kit
(For Beams 4-1/2 - 8-7/8 in. Wide)
IMPORTANT:
Structural Engineer of Record (SEOR)
must perform thorough evaluation of mounting structure
and determine final mounting requirements before fan
is installed. Manufacturer is not liable for any problems
that arise as the result of insufficient structure, including
(but not limited to) vibration, noise, or safety hazards.
Product warranty will be voided at manufacturer’s
discretion if structure is deemed insufficient.
Installations must comply with the following
requirements at a minimum, but SEOR may require
more stringent specifications at their discretion:
Do not use the wood beam mounting kit on wood
beams that are less than 4-1/2 inch wide. For
thinner wood beams, span two or more beams
using structural steel angles or unistrut. Refer to
steel truss or unistrut mounting kit instructions.
Required Loose Components (Included):
• Wood Beam Bracket (2)
Required Components from Bag # 915429:
• 1/2 in. – 13 x 1-1/2 in. Grade 8 Hex Bolt (4)
• 1/2 in. – 13 Grade 8 Nylon Locknut (8)
• 1/2 in. Washer (16)
Hardware/Tools Needed (Not Included):
• 1/2 in. – 13 Grade 8 Hex Bolt (4),
length determined
by wood beam thickness
• Torque Wrench
• 3/4 in. Socket and Wrench
• 3/4 in. Wrench
• Drill and 9/16 in. Drill Bit
1. Locate desired fan hanging location. Using the
supplied wood beam brackets as a template, mark
and drill (4) 9/16 in. holes in the wood beam. Be
sure bottom of brackets are flush or slightly below
bottom of wood beam to effectively connect to the
universal mounting plate. Note that the universal
mounting plate can accommodate beam widths
between 4-1/2 in. and 8-7/8 in..
2. Bolt wood beam brackets into place using (4) grade
8, 1/2 in. – 13 bolts (by others to accommodate
varying material thickness), and supplied (4) 1/2 in.
– 13 nylon locknuts, and (8) 1/2 in. washers. Torque
hardware to 80 ft∙lbf (108.5 N∙m).
1/2 in. WASHER
1/2 in. - 13 GRADE 8
NYLON LOCKNUT
WOOD BEAM
WOOD BEAM
BRACKET
1/2 in. - 13 GRADE 8 HEX BOLT
(BY OTHERS)
TORQUE TO 80 FT∙LBF
(108.5 N∙m)
3. With wood beam brackets installed, line up
universal mounting plate and bolt into wood beam
brackets using supplied (4) 1/2 in. – 13 x 1-1/2 in.
hex bolts, (8) 1/2 in. washers, and (4) 1/2 in. – 13
nylon locknuts.
1/2 in. WASHER
1/2 in. - 13 GRADE 8 NYLON LOCKNUT
WOOD BEAM
DOWNTUBE & MOUNT ASSEMBLY
1/2 in. - 13 x 1-1/2 in. GRADE 8 HEX BOLT
UNIVERSAL MOUNTING PLATE
TORQUE TO 80 FT∙LBF
(108.5 N∙m)
4. Torque hardware to 80 ft∙lbf (108.5 N∙m).
5. Turn to page 22 to continue with Motor/Hub to
Downtube Installation.
Quick Start
Guide
Gener
al
Information
Pr
e-Installation
Mechanical
Installation
Fir
e System
Integr
ation
Electrical
Installation
Fan
Netw
orking
Oper
ation And
Maintenance
Troubleshooting
Refer