Unit Control
[Notes]
At the commissioning parameter setting page, when the state of any function changes, the system
will automatically save this change and this change will remain upon power failure.
Do not modify any commissioning parameter except the approved qualified servicemen, as it
would give birth to adverse effects to the unit.
Commissioning Function Setting
Item
Range
Default
Description
1
Ctrl. state
T-water out/T-room
T-water out
When ―
Remote sensor
‖ is set to ―
With
‖, it
can be set to ―
T-room
‖.
2
2-Way valve
Cool 2-Way valve, On/Off
Off
It will decide the status of the 2-way valve
under the ―
Cool
‖ and ―
Cool + Hot water
‖
modes.
Heat 2-Way valve, On/Off
On
It will decide the status of the 2-way valve
under the ―
Heat
‖ and ―
Heat + Hot water
‖
modes
5
Solar setting
With/Without
Without
1. When the water tank is unavailable,
this setting will be reserved.
2.
When it is set to ―
With
‖, the solar kitting
will work on its own.
3.
When it is set to ―
Without
‖, hot water
by the solar kitting is unavailable.
6
Water tank
With/Without
Without
7
Thermostat
Without/Air/Air+ hot water
Without
1. This setting cannot be interchanged
between ―
Air
‖ and ―
Air+ hot water
‖
directly but via ―
Without
‖ this option
2.
Each time when ―
Air
‖ or ―
Air + hot
water
‖ is switched to ―Without‖, the unit
will go to the OFF status. Meanwhile,
the control will send out ―
OFF
‖
command for consecutive 40 seconds
(it is longer than the communication
error, and the ―
ON
‖ command can be
performed only when 40 seconds have
been expired.
Содержание VERSATI III Series
Страница 1: ...VERSATI Ⅲ Air To Water Heat Pump ...
Страница 5: ...Engineering Data ENGINEERING DATA ...
Страница 10: ...Engineering Data 1 4 Operating Principle 1 4 1 Schematic Diagram ...
Страница 22: ...Design and Selection DESIGN SELECTION ...
Страница 33: ...Unit Control UNIT CONTROL ...
Страница 72: ...Unit Control ...
Страница 76: ...Unit Control 3 3 2 Setting of Main Functions 1 Set mode and temperature ...
Страница 77: ...Unit Control 2 Click Func at the left lower corner in device operation interface to enter advanced settings ...
Страница 79: ...Unit Control 3 3 3 2 Help Click Help and view the operation instructions of the APP ...
Страница 80: ...Unit Control ...
Страница 81: ...Unit Control 3 3 3 3 Feedback Click Feedback to submit feedback ...
Страница 82: ...Installation UNIT INSTALLATION ...
Страница 113: ...Test Operation Troubleshooting Maintenance TEST OPERATION TROUBLESHOOTING MAINTENANCE ...
Страница 117: ...Test Operation Troubleshooting Maintenance 3 Flow Chart of Troubleshooting 3 1 Comp High pressure Protection E1 ...
Страница 118: ...Test Operation Troubleshooting Maintenance 3 2 Comp Low pressure Protection E3 ...
Страница 119: ...Test Operation Troubleshooting Maintenance 3 3 Comp Discharge Temp Protection E4 ...
Страница 120: ...Test Operation Troubleshooting Maintenance 3 4 Overload Protection of Compressor or Driver Error ...
Страница 121: ...Test Operation Troubleshooting Maintenance 3 5 DC Fan Error EF 3 6 Temperature Sensor Error ...
Страница 122: ...Test Operation Troubleshooting Maintenance 3 7 Communication Malfunction E6 ...
Страница 123: ...Test Operation Troubleshooting Maintenance 3 8 Capacity Switch Error Code C5 ...
Страница 125: ...Test Operation Troubleshooting Maintenance IPM or PFC Over temperature Protection Code P8 ...
Страница 127: ...Test Operation Troubleshooting Maintenance ...
Страница 135: ...Test Operation Troubleshooting Maintenance ...