![Gree VERSATI III Series Скачать руководство пользователя страница 66](http://html1.mh-extra.com/html/gree/versati-iii-series/versati-iii-series_service-manual_2260168066.webp)
Unit Control
below.
Error View Page
[Notes]
●The control panel can display real-time errors. And at these pages, all errors will be listed here.
● Each page displays at most 5 pieces of errors. Others can be viewed by touching the page turning
keys.
Error List
No
Full Name
Displayed Name
Code
1
Ambient temperature sensor error
Ambient sensor
F4
2
Defrosting temperature sensor error
Defrost sensor
d6
3
Discharge temperature sensor error
Discharge sensor
F7
4
Suction temperature sensor error
Suction sensor
F5
5
Economizer inlet temperature sensor
Econ. in sens.
F2
6
Economizer outlet temperature sensor
Econ. out sens.
F6
7
Fan error
Outdoor fan
EF
8
High pressure protection
High pressure
E1
9
Low pressure protection
Low pressure
E3
10
High discharge protection
Hi-discharge
E4
11
Capacity DIP switch error
Capacity DIP
c5
12
Communication error between the outdoor and
indoor main boards
ODU-IDU Com.
E6
13
Communication error between the outdoor
main board and the drive board
Drive-main com.
P6
14
Communication error between the display
panel and indoor main board
IDU Com.
E6
15
High pressure sensor error
HI-pre. sens.
Fc
16
Leaving water temperature sensor error for the
plate type heat exchanger of the heat pump
Temp-HELW
F9
Содержание VERSATI III Series
Страница 1: ...VERSATI Ⅲ Air To Water Heat Pump ...
Страница 5: ...Engineering Data ENGINEERING DATA ...
Страница 10: ...Engineering Data 1 4 Operating Principle 1 4 1 Schematic Diagram ...
Страница 22: ...Design and Selection DESIGN SELECTION ...
Страница 33: ...Unit Control UNIT CONTROL ...
Страница 72: ...Unit Control ...
Страница 76: ...Unit Control 3 3 2 Setting of Main Functions 1 Set mode and temperature ...
Страница 77: ...Unit Control 2 Click Func at the left lower corner in device operation interface to enter advanced settings ...
Страница 79: ...Unit Control 3 3 3 2 Help Click Help and view the operation instructions of the APP ...
Страница 80: ...Unit Control ...
Страница 81: ...Unit Control 3 3 3 3 Feedback Click Feedback to submit feedback ...
Страница 82: ...Installation UNIT INSTALLATION ...
Страница 113: ...Test Operation Troubleshooting Maintenance TEST OPERATION TROUBLESHOOTING MAINTENANCE ...
Страница 117: ...Test Operation Troubleshooting Maintenance 3 Flow Chart of Troubleshooting 3 1 Comp High pressure Protection E1 ...
Страница 118: ...Test Operation Troubleshooting Maintenance 3 2 Comp Low pressure Protection E3 ...
Страница 119: ...Test Operation Troubleshooting Maintenance 3 3 Comp Discharge Temp Protection E4 ...
Страница 120: ...Test Operation Troubleshooting Maintenance 3 4 Overload Protection of Compressor or Driver Error ...
Страница 121: ...Test Operation Troubleshooting Maintenance 3 5 DC Fan Error EF 3 6 Temperature Sensor Error ...
Страница 122: ...Test Operation Troubleshooting Maintenance 3 7 Communication Malfunction E6 ...
Страница 123: ...Test Operation Troubleshooting Maintenance 3 8 Capacity Switch Error Code C5 ...
Страница 125: ...Test Operation Troubleshooting Maintenance IPM or PFC Over temperature Protection Code P8 ...
Страница 127: ...Test Operation Troubleshooting Maintenance ...
Страница 135: ...Test Operation Troubleshooting Maintenance ...