Unit Control
default value also will change as the corresponding condition changes.
●
All parameters will be memorized upon power failure.
Parameter Setting
No
Full Name
Displayed Name
Range
Range
Default
Remarks
(
℃
)
(°F)
1
Leaving water
temperature for
cooling(T1)
WOT-Cool
7~25
℃
45~77
℉
18
℃
/64
℉
2
Leaving water
temperature for heating
(T2)
WOT-Heat
20~60
℃
68~140
℉
45
℃
/113
℉
High-temp
series units
20~55
℃
68~140
℉
45
℃
/113
℉
Normal-temp
series units
3
Room temperature for
cooling (T3)
RT-Cool
18~30
℃
64~86
℉
24
℃
/75
℉
4
Room temperature for
heating (T4)
RT-Heat
18~30
℃
64~86
℉
20
℃
/68
℉
5
Water tank
temperature(T5)
T-water tank
40~80
℃
104~176
℉
50
℃
/122
℉
6
Leaving water
temperature difference
for cooling (
Δt1)
ΔT-Cool
2~10
℃
36~50
℉
5
℃
/41
℉
7
Leaving water
temperature difference
for cooling (
Δt2)
ΔT-Heat
2~10
℃
36~50
℉
10
℃
/50
℉
8
Leaving water
temperature difference
for water heating (
Δt3)
ΔT-hot water
2~8
℃
36~46
℉
5
℃
/41
℉
9
Room temperature
control difference (
Δt4)
ΔT-Room temp
1~5
℃
34~41
℉
2
℃
/36
℉
3.2.4 Commissioning Parameter Setting
[Operation Instructions]
★
1. At the menu page, by touching ―
Commission
‖, it will access to the commissioning parameter page,
where the left side is for the function setting and the right side is for the parameter setting, as shown in
the figure below.
Содержание VERSATI III Series
Страница 1: ...VERSATI Ⅲ Air To Water Heat Pump ...
Страница 5: ...Engineering Data ENGINEERING DATA ...
Страница 10: ...Engineering Data 1 4 Operating Principle 1 4 1 Schematic Diagram ...
Страница 22: ...Design and Selection DESIGN SELECTION ...
Страница 33: ...Unit Control UNIT CONTROL ...
Страница 72: ...Unit Control ...
Страница 76: ...Unit Control 3 3 2 Setting of Main Functions 1 Set mode and temperature ...
Страница 77: ...Unit Control 2 Click Func at the left lower corner in device operation interface to enter advanced settings ...
Страница 79: ...Unit Control 3 3 3 2 Help Click Help and view the operation instructions of the APP ...
Страница 80: ...Unit Control ...
Страница 81: ...Unit Control 3 3 3 3 Feedback Click Feedback to submit feedback ...
Страница 82: ...Installation UNIT INSTALLATION ...
Страница 113: ...Test Operation Troubleshooting Maintenance TEST OPERATION TROUBLESHOOTING MAINTENANCE ...
Страница 117: ...Test Operation Troubleshooting Maintenance 3 Flow Chart of Troubleshooting 3 1 Comp High pressure Protection E1 ...
Страница 118: ...Test Operation Troubleshooting Maintenance 3 2 Comp Low pressure Protection E3 ...
Страница 119: ...Test Operation Troubleshooting Maintenance 3 3 Comp Discharge Temp Protection E4 ...
Страница 120: ...Test Operation Troubleshooting Maintenance 3 4 Overload Protection of Compressor or Driver Error ...
Страница 121: ...Test Operation Troubleshooting Maintenance 3 5 DC Fan Error EF 3 6 Temperature Sensor Error ...
Страница 122: ...Test Operation Troubleshooting Maintenance 3 7 Communication Malfunction E6 ...
Страница 123: ...Test Operation Troubleshooting Maintenance 3 8 Capacity Switch Error Code C5 ...
Страница 125: ...Test Operation Troubleshooting Maintenance IPM or PFC Over temperature Protection Code P8 ...
Страница 127: ...Test Operation Troubleshooting Maintenance ...
Страница 135: ...Test Operation Troubleshooting Maintenance ...