Engineering Data
GRS-CQ14Pd/NhG-K
25
3.3
2×3.3
GRS-CQ16Pd/NhG-K
25
3.3
2×3.3
GRS-CQ10Pd/NhG-M
380-415V,3N~,50Hz
16
2.1
4×2.1
GRS-CQ12Pd/NhG-M
16
2.1
4×2.1
GRS-CQ14Pd/NhG-M
16
3.3
4×2.1
GRS-CQ16Pd/NhG-M
16
3.3
4×2.1
Notes
①
Leakage Switch is necessary for additional installation. If circuit breakers with leakage
protection are in use, action response time must be less than 0.1 second, leakage circuit must
be 30mA.
②
The above selected power cable diameters are determined based on assumption of distance
from the distribution cabinet to the unit less than 75m. If cables are laid out in a distance of 75m
to 150m, diameter of power cable must be increased to a further grade.
③
The power supply must be of rated voltage of the unit and special electrical line for
air-conditioning.
④
All electrical installation shall be carried out by professional technicians in accordance with the
local laws and regulations.
⑤
Ensure safe grounding and the grounding wire shall be connected with the special grounding
equipment of the building and must be installed by professional technicians.
⑥
The specifications of the breaker and power cable listed in the table above are determined
based on the maximum power (maximum amps) of the unit.
⑦
The specifications of the power cable listed in the table above are applied to the
conduit-guarded multi-wire copper cable (like, YJV XLPE insulated power cable) used at 40°C
and resistible to 90°C (see IEC 60364-5-52). If the working condition changes, they should be
modified according to the related national standard.
⑧
The specifications of the breaker listed in the table above are applied to the breaker with the
working temperature at 40°C. If the working condition changes, they should be modified
according to the related national standard.
1.5.5 Capacity Correction
Cooling Capacity Correction
GRS-CQ4.0Pd/NhG-K, GRS-CQ6.0Pd/NhG-K, GRS-CQ6.0Pd/NhG-K, GRS-CQ10Pd/NhG-K,
GRS-CQ12Pd/NhG-K,GRS-CQ14Pd/NhG-K, GRS-CQ16Pd/NhG-K, GRS-CQ10Pd/NhG-M,
GRS-CQ12Pd/NhG-M, GRS-CQ14Pd/NhG-M, GRS-CQ16Pd/NhG-M
Performance correction
Leaving Chilled Water
℃
(
℉
)
Ambient Temperature
℃
(
℉
)
25(77)
30(86)
35(95)
40(104)
45(113)
5(41.0)
0.995
0.955
0.905
0.855
0.805
6(42.8)
1.045
1.005
0.955
0.905
0.855
7(44.6)
1.090
1.050
1.000
0.950
0.900
8(46.4)
1.145
1.102
1.052
1.000
0.950
9(48.2)
1.190
1.150
1.100
1.050
1.002
10(50.0)
1.245
1.200
1.150
1.100
1.050
Содержание VERSATI III Series
Страница 1: ...VERSATI Ⅲ Air To Water Heat Pump ...
Страница 5: ...Engineering Data ENGINEERING DATA ...
Страница 10: ...Engineering Data 1 4 Operating Principle 1 4 1 Schematic Diagram ...
Страница 22: ...Design and Selection DESIGN SELECTION ...
Страница 33: ...Unit Control UNIT CONTROL ...
Страница 72: ...Unit Control ...
Страница 76: ...Unit Control 3 3 2 Setting of Main Functions 1 Set mode and temperature ...
Страница 77: ...Unit Control 2 Click Func at the left lower corner in device operation interface to enter advanced settings ...
Страница 79: ...Unit Control 3 3 3 2 Help Click Help and view the operation instructions of the APP ...
Страница 80: ...Unit Control ...
Страница 81: ...Unit Control 3 3 3 3 Feedback Click Feedback to submit feedback ...
Страница 82: ...Installation UNIT INSTALLATION ...
Страница 113: ...Test Operation Troubleshooting Maintenance TEST OPERATION TROUBLESHOOTING MAINTENANCE ...
Страница 117: ...Test Operation Troubleshooting Maintenance 3 Flow Chart of Troubleshooting 3 1 Comp High pressure Protection E1 ...
Страница 118: ...Test Operation Troubleshooting Maintenance 3 2 Comp Low pressure Protection E3 ...
Страница 119: ...Test Operation Troubleshooting Maintenance 3 3 Comp Discharge Temp Protection E4 ...
Страница 120: ...Test Operation Troubleshooting Maintenance 3 4 Overload Protection of Compressor or Driver Error ...
Страница 121: ...Test Operation Troubleshooting Maintenance 3 5 DC Fan Error EF 3 6 Temperature Sensor Error ...
Страница 122: ...Test Operation Troubleshooting Maintenance 3 7 Communication Malfunction E6 ...
Страница 123: ...Test Operation Troubleshooting Maintenance 3 8 Capacity Switch Error Code C5 ...
Страница 125: ...Test Operation Troubleshooting Maintenance IPM or PFC Over temperature Protection Code P8 ...
Страница 127: ...Test Operation Troubleshooting Maintenance ...
Страница 135: ...Test Operation Troubleshooting Maintenance ...