Installation
Example 2:
The unit is installed on the highest spot of the water system and the total water volume is
100L.
As the volume of water system is higher than 75L, it is necessary to adjust the pressure of the
expansion vessel be lower.
The formula of calculating pressure
Pg=(H/10+0.3)=(0/10+0.3)=0.3 Bar
The maximum volume of the water system is about 410L. As the actual volume of the water system is
118L, the expansion vessel meets the installing requirement.
Adjust the pre-set pressure of the expansion vessel from 1.5Bar to 0.3Bar.
4.6.4 Selection of expansion vessel
Formula:
V--- Volume of expansion vessel
C--- Total water volume
P1--- Pre-set pressure of expansion vessel
P2-- The highest pressure during running of the system (that is the action pressure of safety valve.)
e---The expansion factor of water (the difference between the expansion factor of the original water
temperature and that of highest water temperature.)
Water expansion factor in different temperature
Temperature
Expansion factor e
0
0.00013
4
0
10
0.00027
20
0.00177
30
0.00435
40
0.00782
45
0.0099
50
0.0121
55
0.0145
60
0.0171
65
0.0198
70
0.0227
75
0.0258
80
0.029
85
0.0324
90
0.0359
95
0.0396
100
0.0434
Содержание VERSATI III Series
Страница 1: ...VERSATI Ⅲ Air To Water Heat Pump ...
Страница 5: ...Engineering Data ENGINEERING DATA ...
Страница 10: ...Engineering Data 1 4 Operating Principle 1 4 1 Schematic Diagram ...
Страница 22: ...Design and Selection DESIGN SELECTION ...
Страница 33: ...Unit Control UNIT CONTROL ...
Страница 72: ...Unit Control ...
Страница 76: ...Unit Control 3 3 2 Setting of Main Functions 1 Set mode and temperature ...
Страница 77: ...Unit Control 2 Click Func at the left lower corner in device operation interface to enter advanced settings ...
Страница 79: ...Unit Control 3 3 3 2 Help Click Help and view the operation instructions of the APP ...
Страница 80: ...Unit Control ...
Страница 81: ...Unit Control 3 3 3 3 Feedback Click Feedback to submit feedback ...
Страница 82: ...Installation UNIT INSTALLATION ...
Страница 113: ...Test Operation Troubleshooting Maintenance TEST OPERATION TROUBLESHOOTING MAINTENANCE ...
Страница 117: ...Test Operation Troubleshooting Maintenance 3 Flow Chart of Troubleshooting 3 1 Comp High pressure Protection E1 ...
Страница 118: ...Test Operation Troubleshooting Maintenance 3 2 Comp Low pressure Protection E3 ...
Страница 119: ...Test Operation Troubleshooting Maintenance 3 3 Comp Discharge Temp Protection E4 ...
Страница 120: ...Test Operation Troubleshooting Maintenance 3 4 Overload Protection of Compressor or Driver Error ...
Страница 121: ...Test Operation Troubleshooting Maintenance 3 5 DC Fan Error EF 3 6 Temperature Sensor Error ...
Страница 122: ...Test Operation Troubleshooting Maintenance 3 7 Communication Malfunction E6 ...
Страница 123: ...Test Operation Troubleshooting Maintenance 3 8 Capacity Switch Error Code C5 ...
Страница 125: ...Test Operation Troubleshooting Maintenance IPM or PFC Over temperature Protection Code P8 ...
Страница 127: ...Test Operation Troubleshooting Maintenance ...
Страница 135: ...Test Operation Troubleshooting Maintenance ...