Additional Features
Contact Sense
5-8
SpectraComm ADT
076R172-000
Installation and Operation Manual
Issue 6
Input Contact Sense Procedure
This procedure configures up to eight individual contacts at the rear panel DB25 interface for input
contact sensing, using the contact number
c
[#] in the command string. If desired, you can configure
a parameter for all contacts at once by typing
all
in place of
c
[#].
1. Connect the external device to the SC-ADT rear panel DB25 interface as described in
Chapter 2, Installation & Connections
of this manual.
•
for SC-ADT rear panel connection details.
•
for DB25 interface pinouts.
2. At the SC-ADT, set the normal operating state of each contact by typing:
configure contact normal-state c
[#]
[
NO
or
NC
]
where
c
[#] is a contact 1 through 8. The normal state for each is Normally Open (
NO
) or
Normally Closed (
NC
). Default is Normally Open.
3. If desired, enter an alphanumeric description for the individual contact by typing:
configure contact description c
[#]
[“contact description”]
Note
If a space is desirable in the description, you must use a double-quoted string, as shown above.
4. Enable the individual contact by typing:
configure contact enable c
[#]
and
for each dry contact device to be monitored by the SC-ADT.
6. Disable any unused contacts at the DB25 connector by typing:
configure contact disable c
[#]
7. The SC-ADT is now monitoring the enabled input contact interfaces at the DB25 connector.
•
To view the current configuration parameters and status of all contact interfaces including
current state and alarm status, type:
show contact
•
To manually clear an active alarm condition, type:
configure contact clear
c
[#]
If the condition persists after clearing the alarm, a new alarm is generated, sending a new SNMP trap.
Figure 5-4
Status Display for Environmental Inputs (DB25 Interface)
SC-ADT# show contact
____________________________Contact Status_____________________________
Contact Admin Normal Current Alarm
Name State State State Status
---------- ----- ----- ------- ------
contact1 ON NO Open Clear
contact2 ON NO Open Clear
contact3 ON NO Open Clear
contact4 ON NO Open Clear
contact5 ON NO Open Clear
contact6 ON NO Open Clear
contact7 ON NO Open Clear
contact8 ON NO Open Clear
Contact Description
-----------------------------------------------------------------------
contact1 Door open
contact2 Temperature High
contact3
contact4
contact5
contact6
contact7
contact8