86 • Chapter 5 Quick Start Up Guide
ARTDrive V2 series - Instruction Manual
Run Motor autotune
(Motor parameters
measurement)
If required:
set the motor V/f curve
If required:
set the encoder
parameters
Set the drive main
command
If required:
select Local / Remote
command source
B STARTUP / B00 Drv & Mot config / B0E Autotune
Select one of two Autotune procedures available:
•
B0E.00 - Complete rot
: complete self-tuning of drive
current and flux loops with moving motor shaft.
•
B0E.01 - Complete still
: complete self-tuning of
drive current and flux loops with stopped motor shaft.
Note!
When motor is coupled to gearbox and load on the motor
shaft is installed, use
Complete still
.
When motor is uncoupled or gearbox does not represent more than
10% of load and motor shaft is unloaded, use
Complete rot
.
Press
[Enter]
and
[I]
” keys to run the procedure
(12 drive terminal must be cycle to +24Vdc).
Wait up to “Autotune End” message will be displayed,
then press three times
[Escape]
key.
B STARTUP / B00 Drv & Mot config / B0F V/f cfg
Enter the parameters:
•
B0F.00 - V/f voltage
to set the V/f base voltage
•
B0F.01 - V/f frequency
to set the V/f base frequency
•
B0F.02 - Voltage boost
to set the torque boost.
B STARTUP / B00 Drv & Mot config / B0G Encoders
Enter the parameters:
•
B0G.00 - Std enc type
to set the fbk encoder type.
•
B0G.01 - Std enc pulses
to set the encoder pulses.
•
B0G.02 - Std enc supply
to set the encoder supply
voltage.
B STARTUP / B01 Main cmds
Enter the
B01.00 - Commands select
parameter to
control the drive via:
•
[0] TerminalLevel
terminal strip using a Level sensitive
signals
•
[1] TerminalEdge
terminal strip using a Edge sensitive
signals
•
[2] DigitalLevel
dedicated for application card
•
[3] DigitalEdge
dedicated for application card
•
[4] I O keys
keyboard using the
[I], [O]
keys;
terminal 12 to and terminal 13 to
24Vdc are required
B STARTUP / B01 Main cmds
Enter the
B01.01 - Term Local src
parameter select the
Local/Remote command through digital input desired.
For more details see paragraph 7.3, Index
B01.01.
Operation
Operation
Step
11
12
13
14
15
Содержание ARTDrive Vector V2 400Vac Series
Страница 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Страница 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Страница 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Страница 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Страница 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Страница 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...