Chapter 6 Parameter • 121
Resistor short time overload rating
= 5 time quarter minute (5 time continuous amps
for 15 secs)
Set parameters:
Bu resistance
=
50
I
2
* R
Bu res cont pwr
=
11.25 kW (15
2
* 50)
Bu res OL time
=
15 secs
Bu res OL factor
=
25 (power = 12 R, 5 times overload current squared =
25)
B0I.04 BU res OL factor
N/A
RWZ
D.Size
1.2/20
FK
V-F-S-B
Easy 1730
Resistance allowed overload time referring to the overload power. The control of the
external braking unit and of the resistance I2t protection is independent of BU type (BU
digital output command, is available, on the regulation card terminals ).
B0J
STARTUP / Drv & Mot config / SpdReg G
N
OTE
!
Menu accessible with Access Level = FULL.
It allows to perform the speed regulator gain calculation. Inertia must be entered throught
the
B0J.01 - Calc Inertia
parameter or specifying parameters.
BOJ.00 Calc method
N/A
RWZ
0
0/1
DK
F-S-B
Full
2048
With
Calc method
two gain calculation methods can be selected:
[0] VariableBandw
Speed regulation bandwidth is internally selected according to the principle
that bandwidth is decreased as inertia is increased
[1] FixedBandw
Speed regulation bandwidth is specified by
B0J.02 - Bandwidth
parameter
N
OTE
!
BOJ.00 - Calc method
and
0J.02 - Bandwidt
parameters are also valid for Speed
Regulator Auto tune procedure.
B0J.01 Calc Inertia
[kgm2] RWZ
D.Size
0/0
FK
F-S-B
Full
2610
Inertia of the load in kg * m
2
.
B0J.02 Bandwidth
[rad/s] RWZ
50
1/300
FK
F-S-B
Full
2049
Speed regulator bandwidth. Higher bandwidth value makes motor respond faster and
overall result is more stiff control.
B0K.00
B0K.00 Abort ?
Full
Reload of last saved database. The data set after saving process are not stored.
It is advisable to carry out a
Save
parameters befor entering the
Startup / Drv & mot
config
menu.
Содержание ARTDrive Vector V2 400Vac Series
Страница 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Страница 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Страница 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Страница 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Страница 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Страница 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...