ARTDrive V2 series - Instruction Manual
Chapter 4 Wiring Procedure • 73
η
m
:
motor rated efficiency
-
at no load, it depends on the iron losses, on mechanical losses, and stator
joule losses. The sum of these terms is about 50% of the full load losses.
Full load losses P
lfl
are:
P
lfl
P
m
1 -
h
m
h
m
=
Maximum power supply drop out time (Buffer time/voltage failure buffer) of
ARTDrive is achieved by adding the maximum recommended capacitance to
the DC bus.
The following table show the maximum power supply drop out time for different
Undervoltage thresholds and inverter sizes. The meaning of the symbols in the
colums is as follows:
C
std
= internal capacitance in
μ
F,
C
ext
max = external total capacitance in
μ
F,
T
buff
= max drop out time in sec.,
P
SMPS
= power supply watts,
U
buff
= volts threshold to disable drive operation,
U
min
= min DC volts that will support the power supply
Where T
buff
is defined by the formula:
T
buff
(C +
std
C
max) (U
- U
)
ext
buff
min
2
2
2 P
10
SMPS
6
=
Table 4.10.1: Drive Trip Times, 230-V Threshold
Size
Psmps [W]
C
std
[µF]
C
ext
max [µF]
U
buff
[V]
U
min
[V]
T
buff
[sec.]
4220
70
1800
4500
230
200
0.58
4300
70
2200
4500
230
200
0.62
4370
70
3300
4500
230
200
0.72
5450
70
4950
4500
230
200
0.87
5550
70
4950
4500
230
200
0.87
6750
70
6600
0
230
200
0.61
7900
70
6600
0
230
200
0.61
71100
70
9900
0
230
200
0.91
71320
70
14100
0
230
200
1.3
81600
70
14100
0
230
200
1.3
av
y
4225
Содержание ARTDrive Vector V2 400Vac Series
Страница 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Страница 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Страница 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Страница 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Страница 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Страница 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...