20 • Chapter 2 Inspection Procedure,...
ARTDrive V2 series - Instruction Manual
Disposal of the Device
The AVy Drive can be disposed as electronic scraps in accordance with the
currently valid national regulations for the disposal of electronic parts.
The plastic covering of the Drives, up to sizes 3150 (230/480Vac series) and
2002 to 3020 (575Vac series), are recyclable: the material used is >ABS+PC<.
2.3.2 AC Input/Output Connection
- AVy...-4 (230/480Vac)
Suitable for use on a circuit capable of delivering not more than (*) rms (see
table below) Symmetrical Amperes, 400 Vac +10% maximum:
Models
Max input short circuit current
1007 to 4370
(*) :
5000 A
5450 to 71320
(*) :
10000 A
81600
(*) :
18000 A
- AVy...-5 (575Vac)
Suitable for use on a circuit capable of delivering not more than (*) rms (see
table below) Symmetrical Amperes, 575 Vac +10% maximum:
Models
Max input short circuit current
2002 to 4040
(*) :
5000 A
5050 to 7150
(*) :
10000 A
8200
(*) :
18000 A
Also the insertion of a Mains inductance should be take into account (see
chapter 4.7.1).
No external connection of the regulator power supply to the existing AC Input
supply is required since the power supply is taken from the DC Link circuit.
However, a 24V backup input for the regulator power supply can be used if it is
desired to monitor status and diagnostic information across a power failure.
When commissioning, set the
B0B.00 - Mains voltage
parameter to the value
of the AC Input voltage concerned. This automatically sets the threshold for the
Undervoltage and Overvoltage alarms to the appropriate levels.
N
OTE
!
A “
Sequencer reset
” command is required to restart the drive when input voltage
is restored.
N
OTE
!
In some cases AC Input chokes, and possibly noise suppression filters should
be fitted on the AC Input side of the device in order to operate the AVy Drive.
See chapter “Chokes/Filters”.
Adjustable Frequency Drives and AC Input filters have ground discharge
currents greater then 3.5 mA. EN 50178 specifies that with discharge currents
greater than 3.5 mA the protective conductor ground connection (PE1) must
be fixed type.
Содержание ARTDrive Vector V2 400Vac Series
Страница 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Страница 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Страница 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Страница 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Страница 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Страница 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...