ARTDrive V2 series - Instruction Manual
Chapter 4 Wiring Procedure • 49
no.
Strip X1
Function
max
1 - 2
Analog input 1
Programmable/configurable analog differential input. Signal:
terminal 1.
Reference point: terminal 2.
D00.00 - Ramp ref 1 src =
001 -
AI 1 output (default)
3 - 4
Analog input 2
Programmable/configurable analog differential input. Signal:
terminal 3.
Reference point: terminal 4. Default setting: none
5 - 6
Analog input 3
Programmable/configurable analog differential input. Signal:
terminal 5.
Reference point: terminal 6. Default setting: none. (1)
7
+10V
Reference v10V; Reference point: terminal 9
+10V/10mA
8
-10V
Reference voltage -10V; Reference point: terminal 9
-10V/10mA
9
0V
Internal 0V and reference point for±10V
-
12
Enable / Digital input 0
Inverter enable, active=high. Concurrentl
y
, it can be used as a
programmable input. (Default none)
13
Digital input 1
Programmable input:
C00.07
-
ForwardStart src =
003 - DI 1 mon
(default)
14
Digital input 2
Programmable input:
C00.08
-
Reverse src =
004 - DI 2 mon
(default)
15
Digital input 3
Programmable input:
C00.09
-
Stop src =
005 - DI 3 mon
(default)
16
COM D I/O
Reference point for digital inputs and outputs, term.12...15,
36...39, 41...42
-
18
0 V 24
Reference point for + 24V OUT suppl
y
, terminal 19
-
19
+24V OUT
+24V suppl
y
output. Reference point: terminal 18 or 27 or 28
+22…28V / 120mA
@ 24V
no.
Strip X1
Function
max
21
Analog output 1
Programmable analog output:
C08.00 - AO 1 src
=
000 - NULL
(default)
±10V/5mA
22
0V
Internal 0V and reference point for terminals 21 and 23
-
23
Analog output 2
Programmable analog output:
C09.00 - AO 2 src
=
000 - NULL
(default)
±10V/5mA
26
BU comm. Output
VeCon controlled BU-... braking units command. Ref. point:
term.27.
+28V/15mA
27
0 V 24
Reference point for BU-... command, terminal 26
-
28
RESERVED
29
RESERVED
36
Digital input 4
Programmable digital inputs; default setting: none
37
Digital input 5
Programmable digital inputs; default setting: none
38
Digital input 6
Progr. digital input; def. setting: none. Configurable as 2nd
encoder index qualifier (setting via S30 jumper, ”Digital input
6” parameter must be set as not used)
39
Digital input 7
Programmable digital input; default setting: none.
Configurable as 1st encoder index qualifier (”Digital input 7”
parameter must be set as not used ).
41
Digital output 2
Programmable digital outputs:
C19.02 - DO 2 src
=
000 - NULL
(default)
+30V/40mA
42
Digital output 3
Programmable digital outputs:
C19.03 - DO 3 src
=
000 - NULL
(default)
+30V/40mA
46
Suppl
y
D O
Suppl
y
input for digital outputs on terminals 41/42. Ref. point:
term.16.
+30V/80mA
78 - 79
Motor PTC
Motor PTC sensing for overtemperature (cutoff R1k if used)
1.5mA
no.
Strip X2
Function
max
80 - 82
Digital output 0 Rela
y
Potential- free rela
y
contact, programmable output:
C19.00 - DO 0 src
=
008 - Drive OK
(default) when closed
250V AC / 1A
83 - 85
Digital output 1 Rela
y
Potential- free rela
y
contact, programmable output:
C19.01 - DO 1 src
=
029 - Spd is zero
(default) when closed
250V AC / 1A
±10V / 0.25mA
(20mA when current
loop input)
+30V
3.2mA @ 15V
5mA @ 24V
6.4mA @ 30V
+30V
3.2mA @ 15V
5mA @ 24V
6.4mA @ 30V
Содержание ARTDrive Vector V2 400Vac Series
Страница 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Страница 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Страница 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Страница 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Страница 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Страница 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...