ARTDrive V2 series - Instruction Manual
Chapter 6 Parameter • 213
zero and stops its integrating activity.
ª
ª
ª
ª
ª
Pick List 3
F01.10 Spd reg enable
N/A
RWSZ 1
0/1
DP
V-F-S-B
Easy 7059
Enabling of the speed regulator:
[0] Disabled
[1] Enabled
F01.20 Spd I=0 mon
N/A
R
0
0/1
PV
F-S-B
Full
7055
State monitor for the command Spd I=0.
F01.21 Spd PI=0 mon
N/A
R
0
0/1
PV
F-S-B
Full
7057
State monitor for the command Spd PI=0.
F02 SPEED REG / Spd ratio
N
OTE
!
Menu accessible with Access Level = FULL
The block function allows to set the speed ratio value, through
F02.01 - Speed ratio src
source.
F02.02 - Dig spd Ratio
with a % value is standard connected, but, anyway, also
the connection of analog and digital signals is possible.
Its default value is 100%, corresponding to the multiply 1 factor.
F02.01 Speed ratio src
N/A
RWS
Ipa7044
Plist13
PIN
F-S-B
Full
7052
Ipa 7044 - Dig speed ratio = Default
It select the origin of the signal of speed ratio value.
ª
ª
ª
ª
ª
Pick List 13
F02.02 Dig spd Ratio
[%]
RWS
100
0/200
PV
F-S-B
Full
7044
Digital speed ratio value, selectable through Pick List 13 of
F02.01 - Speed ratio src
.
ª
ª
ª
ª
ª
Pick List 13
F02.03 Speed ratio mon
[%]
R
0.00
0.00/0.00
PP
F-S-B
Full
7048
Displaying of Speed ratio signal.
Содержание ARTDrive Vector V2 400Vac Series
Страница 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Страница 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Страница 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Страница 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Страница 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Страница 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...