ARTDrive V2 series - Instruction Manual
Chapter 6 Parameter • 237
FLUX / Output Voltage Reference control
N
OTE
!
Menu accessible with Access Level = FULL
The Function allows the regulation of the flux in the constant power area where a voltage
margin must be available for the regulation.
This value is usually equal to 2% of the maximum output voltage.
A higher value allows a faster response of the voltage regulator but with a lower amount
of available voltage on the output.
A lower value allows a higher output voltage with a decrease of the dynamic
performances.
The
H02.00 - Outvlt lim src
source allows to select the function control signal. In the
standard configuration the source is connected to
H02.10 - Dig Outvlt lim
, internal
value. Via
H02.10 - Dig Outvlt lim
parameter, it is also possible to control the maximum
value of the output voltage and to state, therefore, the starting voltage of the discharge
point (380V standard). This value can not be higher than the one stated by
H02.12 -
Available Outvlt
.
The available voltage margin is stated via the
H02.11 - Dyn vlt margin
parameter.
As for the normalized value see paragraph 6.1.3 Normalizations Signal.
N
OTE
!
The Function is active only in a Sensorless and Field oriented mode.
H02 FLUX / OutVltRef
H02.00 Outvlt lim src
N/A
RWS
Ipa1140
PList42
PIN
F-S-B
Full
1141
Ipa 1140 - Dig Outvlt lim = Default
It select the origin of Output Voltage Reference control signal.
ª
ª
ª
ª
ª
Pick List 42
H02.10 Dig Outvlt lim
[V]
RWS
Calc
Calc/Calc
PV
F-S-B
Full
1140
Internal digital value of Output Voltage Reference
H02.11 Dyn vlt margin
[%]
RWS
2
1/10
PV
F-S-B
Full
1130
Voltage margin for the flux regulator.
H02.12 Available Outvlt
[V]
R
0.00
0.00/-
PV
F-S-B
Full
1170
Monitor for the maximum available output voltage. It is calculated directly starting from
the DC link voltage.
H02.13 Inuse Outvlt Ref
[V]
R
0.00
0.00/-
PV
F-S-B
Full
1180
Limit in use on the output voltage. It is calculated as follows:
-
The starting point is the
H02.12 - Available Outvlt
.
-
This is limited by the
H02.10 - Dig Outvlt lim
Содержание ARTDrive Vector V2 400Vac Series
Страница 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Страница 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Страница 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Страница 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Страница 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Страница 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...