Index
MENU
MENU
MENU
MENU
MENU
[Unit] Access Default
Min/Max
Format Reg.Mode Level Ipa
Parameter Name
Description
ARTDrive V2 series - Instruction Manual
Chapter 6 Parameter • 259
L17 ALARM CFG / FwRevCtrl
It trips when the Forward Reverse control “truth table” is not satisfied; see
C00.25 - FRC
cmd mode
description in the INTERFACE menu section.
L17.00 FRC activity
N/A
RWS
3
1/6
DP
V-F-S-B
Easy 9086
Forward Reverse control activity:
[1] Ignore
[2] Warning
[3] Disable drive
[4] Stop
[5] Fast stop
[6] Curr limstp
L17.01 FRC hold off
[ms]
RWS
32
0/30000
PP
V-F-S-B
Easy 9607
Forward Reverse control hold off
L18 ALARM CFG / Over Spd
It trips when the speed of the motor exceeded speed limit threshold.
L18.00 OS activity
N/A
RWS
3
2/6
DP
V-F-S-B
Easy 9220
Overspeed activity:
[2] Warning
[3] Disable drive
[4] Stop
[5] Fast stop
[6] Curr limstp
L18.01 OS threshold
[rmp] RWS
Calc
0.00/Calc
PP
V-F-S-B
Easy 9221
Overspeed threshold.
L18.02 OS hold off
[ms]
RWS
0
0/30000
PP
V-F-S-B
Easy 9608
Overspeed hold off.
L19 ALARM CFG / SFbk loss
It trips when the speed feedback is not detected or encoder supply failed.
L19.00 SFL activity
N/A
RWS
3
1/6
DP
V-F-S-B
Easy 9042
Spd fbk loss activity:
[1] Ignore
[2] Warning
[3] Disable drive
Содержание ARTDrive Vector V2 400Vac Series
Страница 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Страница 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Страница 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Страница 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Страница 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Страница 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...