Designation
Description
Conductor cross-section for connection
terminal strip
up to 1.5 mm
2
Required cable diameter for cable gland
Ø 6 mm - Ø 12 mm
Hint!
The electric cable must be long enough so that the control top can be
removed via the switch bar!
The cables must be suitable for use in the temperature range -20 °C to
+60 °C!
Hint!
Cables with sheathing or marking in "light blue" colour must be used,
as the "intrinsically safe connection cables" must always be marked
with this colour!
6.4.3
Electrical wiring
6.4.3.1 Terminal strip assignment in relation to the order code
The following terminal strip assignment must be observed in relation to the order
code:
External connection solenoid valves
Order code
Terminal strip
TE20 N 2 E E/X***
--
TE20 R 2 E E/X***
V1-/V1+
TE20 I 2 E E/X***
V1-/V1+ and V2-/V2+
TE20 J 2 E E/X***
V1-/V1+ and V3-/V3+
TE20 L 2 E E/X***
V1-/V1+ and V2-/V2+ and V3-/V3+
External connection two-wire proximity sensor
Order code
Terminal strip
TE20 N/R/I/J/L 2 E E/X/0***
R1-/R1+ and R2-/R2+
6.4.3.2 Terminal strip designation and separate intrinsically safe circuits
Intrinsically safe external connections
The external connection must be supplied by intrinsically safe circuits.
► Isolating switch amplifiers (ignition protection barriers) must be installed
for the intrinsically safe supply.
Assembly and installation
Electrical connections
430BAL013985EN_6
25.04.2023
53
Содержание T.VIS E-20
Страница 6: ...430BAL013985EN_6 6 25 04 2023...
Страница 9: ...flowcomponents gea com www gea com General Information Contact 430BAL013985EN_6 25 04 2023 9...
Страница 84: ...Fig 42 X signal curve sensor Y current course curve LED brightness Start up 430BAL013985EN_6 84 25 04 2023...
Страница 108: ...14 Dimension sheet control top T VIS E 20 Fig 58 Dimension sheet control top T VIS E 20 430BAL013985EN_6 108 25 04 2023...
Страница 112: ......