Technical data: Inputs for solenoid valve activation 12 VDC
Designation
Description
Control voltage
max. 12 VDC +/-10%
Current consumption, solenoid valve
50 mA**
Pull-in voltage
9.5 VDC
Minimum switching current
37.7 mA
Short-circuit protection
no
Nominal power
0.6 W
Resistance
252 Ω
** Nominal value, reduction by electrical voltage supply through corresponding Ex
valve control module
Technical data: Pilot valve safety classifications (intrinsic safety)
Voltage
(VDC)
Nominal
power
(mW)
Temperature
class
(Group II)
Ui
(VDC)
li
(mA)
Pi
(W)
Li **
(µH)
Ci**
(nF)
24
600
T4
30
210
1.6
negligible
negligible
24
600
T5
30
120
0.9
negligible
negligible
12
600
T4
30
210
1.6
negligible
negligible
12
600
T5
30
120
0.9
negligible
negligible
** Ci and Li do not include the capacitance/inductance of cables to and from
T.VIS E-20.
5.2.4.2 Sensor module data
Intrinsically safe wiring
Errors in the intrinsically safe wiring can lead to serious explosions!
► PLEASE OBSERVE THE TERMINAL DESIGNATION IN CHAPTER
6.4.3.2 (PAGE 48) FOR INTRINSICALLY SAFE WIRING.
Type designation: 221-589.91
Technical data - 2-wire sensor
Designation
Description
Type
BIM-PST-Y1 Group M
Power consumption without operation
≤ 1.2 mA
Power consumption during operation
≥ 2.1 mA
Voltage
nom. 8,2V DC/NAMUR
Short circuit and overload protection
no
Technical data and operating conditions
Technical data
430BAL013985EN_6
42
25.04.2023
Содержание T.VIS E-20
Страница 6: ...430BAL013985EN_6 6 25 04 2023...
Страница 9: ...flowcomponents gea com www gea com General Information Contact 430BAL013985EN_6 25 04 2023 9...
Страница 84: ...Fig 42 X signal curve sensor Y current course curve LED brightness Start up 430BAL013985EN_6 84 25 04 2023...
Страница 108: ...14 Dimension sheet control top T VIS E 20 Fig 58 Dimension sheet control top T VIS E 20 430BAL013985EN_6 108 25 04 2023...
Страница 112: ......