Technical data: Avoidance of electrostatic charge
Fig.12:
Sign above: Information sign for ATEX/UKEX and IECEx certificate / sign below: Information sign for CCCEx certificate
* Relevant for use in dust protection systems
Please make sure that the T.VIS E-20 is installed as described in chapter 6.6. Make sure that the
fitting is earthed above the piping. Make sure that the valve is earthed via the pipe system.
5.2.3
Configuration and specification of the electrical wiring
The maximum cable length and dimensions must be considered based on the
following cable parameters:
Designation
Description
Configuration of the electrical wiring
Terminal strip
Cable specification
Ci cable/cable = 58 pF/m
Ci cable/shielding = 270 pF/m
According to EN 60079-11, the distance between intrinsically safe circuits and earth
must take into account an insulation for 30 V of 0.7 mm.
Conductor cross-section for connection
terminal
up to 1.5 mm
2
Required cable diameter for cable gland
Ø 6 mm - Ø 12 mm
Technical data and operating conditions
Technical data
430BAL013985EN_6
40
25.04.2023