The valve control modules limit current and voltage in the event of a fault, which
allows the solenoid valves to be operated "intrinsically safe" and thus guarantee
separation between Ex and non-Ex areas.
6.4.3.4 Execution and verification of the connection of internal and external circuits
For internal and external connections, the intrinsically safe circuits are defined by
the sensor module and its designation.
The distance within an intrinsically safe circuit and to earthed parts is at least 3
mm.
The distance between different intrinsically safe circuits is at least 6 mm.
The length of the stripping must not exceed 5 mm.
Execution of the connection of external circuits
The standards for the electrical installation of intrinsically safe circuits
according to EN 60079-11 must be observed.
► Check distance between non-insulated strands of at least 3.0 to earthed
parts.
► Check distance between intrinsically safe circuits of at least 6.0 mm.
► Check the length of the stripping of max. 9 mm.
► Check the cables for tight fit.