Technical data: 2-wire sensor safety data (intrinsic safety)
Temperature
class
Ui
(VDC)
li
(mA)
(Resistively
limited)
Pi
(mW)
Li **
(µH)
Ci**
(nF)
T4
20
60
200
150
150
T5
20
60
130
150
150
T85°C
20
60
130
150
150
** Ci and Li do not include the capacitance/inductance of cables to and from
T.VIS E-20.
5.2.5
General Technical Data
Technical data: temperatures and compressed air supply
Designation
Description
Control air
According to ISO 8573-1:2001
- Solids content:
Quality class 6 (recommended)
- Water content:
Quality class 4
max. dew point +3 °C
If the component is operated at a higher altitude or at
low ambient temperatures, the dew point must be
adjusted accordingly.
- Oil content:
Quality class 3,
Preferably oil-free, max. 1 mg of oil in 1m3 air
Air hose
- metric
Material PE-LD
Outside Ø 6 mm
Inside Ø 4 mm
- Inch
Material PA
Outside Ø 6.35 mm
Inside Ø 4.3 mm
Control air pressure
max. 8 bar, min. 2 bar
Sound pressure level with sound absorber max. 72 dB
Weight
max. 1.0 kg
Technical data: Material
Designation
Description
Housing
PA 12/L
Seals
EPDM, FKM and NBR
Technical data and operating conditions
Technical data
430BAL013985EN_6
25.04.2023
43
Содержание T.VIS E-20
Страница 6: ...430BAL013985EN_6 6 25 04 2023...
Страница 9: ...flowcomponents gea com www gea com General Information Contact 430BAL013985EN_6 25 04 2023 9...
Страница 84: ...Fig 42 X signal curve sensor Y current course curve LED brightness Start up 430BAL013985EN_6 84 25 04 2023...
Страница 108: ...14 Dimension sheet control top T VIS E 20 Fig 58 Dimension sheet control top T VIS E 20 430BAL013985EN_6 108 25 04 2023...
Страница 112: ......