10.3.2.3 Removing the Solenoid Valves and the Valve Plate
Fig.46
Requirement:
•
Observe the assignment of cables between the solenoid valve and the sensor
module – solenoid valve Y1 to be connected to terminal Y1+/Y1-.
•
Only use solenoid valves specified in chapter “Technical data”.
Caution!
Risk of burns from the solenoid valve as a result of long switch-
on time and high ambient temperature
Risk of burns from the solenoid valve
► Allow to cool before dismantling.
Carry out the following steps:
1.
Disconnect the cables of the solenoid valve from the terminals of the sensor
module (43).
2.
Undo the screws (66) and separate the solenoid valve (63) from the
pneumatic block (8).
3.
Undo the screws (65.1) and separate the control plate (65) from the
pneumatic block (8).
®
Solenoid valves and valve plates are removed.
®
Done
Servicing
Disassembly
430BAL013985EN_6
92
25.04.2023