4-40
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
FRONT PANEL INTERFACE
CHAPTER 4: INTERFACES
4
Figure 4-48: LED panel 1
Status indicators
•
IN SERVICE
— Indicates that control power is applied, all monitored inputs/outputs and internal systems are fine, and
the relay is in (online) Programmed mode (under
Settings > Product Setup > Installation
)
•
TROUBLE
— Indicates that the relay has detected an internal problem. Check the self-test messages outlined at the
end of the Commands and Targets chapter, and view the event records under
Actual Values > Records
. For a beta /
pre-release, this LED is always on.
•
TEST MODE
— Indicates that the relay is in test mode. For information, see the Test Mode section in the Settings
chapter.
•
TRIP
— Indicates that the selected FlexLogic operand serving as a trip switch has operated. This indicator always
latches; initiate the reset command to reset the latch.
•
ALARM
— Indicates that the selected FlexLogic operand serving as an alarm switch has operated. This indicator never
latches.
•
PICKUP
— Indicates that an element is picked up. This indicator never latches.
Event-cause indicators
Event-cause LEDs are turned on or off by protection elements that have their respective target setting selected as either
“Enabled” or “Latched.” If a protection element target setting is “Enabled,” then the corresponding event cause LEDs
remain on as long as the operand associated with the element remains asserted. If a protection element target setting is
“Latched,” then the corresponding event cause LEDs turn on when the operate operand associated with the element is
asserted and remains on until the
RESET
button on the front panel is pressed after the operand is reset.
All elements that are able to discriminate faulted phases can independently turn off or on the phase A, B, or C LEDs. This
includes phase instantaneous overcurrent, phase undervoltage, and so on. This means that the phase A, B, and C operate
operands for individual protection elements are ORed to turn on or off the phase A, B, or C LEDs.
•
VOLTAGE
— Indicates voltage was involved
•
CURRENT
— Indicates current was involved
•
FREQUENCY
— Indicates frequency was involved
•
OTHER
— Indicates a composite function was involved
•
PHASE A
— Indicates phase A was involved
•
PHASE B
— Indicates phase B was involved
•
PHASE C
— Indicates phase C was involved
•
NEUTRAL/GROUND
— Indicates that neutral or ground was involved
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...