5-40
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
In the example shown, failure of any of the three Ethernet ports triggers the Product Information page to display. With
unauthorized access (such as wrong password), IRIG-B clock failure, or breaker trouble, the Event Records display. When a
breaker opens, a single-line diagram displays. For the Ethernet and IRIG-B failure operation to work, these functions also
have been enabled under
Settings > Product Setup > User-Programmable Self Tests
.
Figure 5-12: Configurable navigation editor
To use the feature, select a
CONDITION
, select an
ACTIVATE PAGE
, then save.
CONDITION
Range: OFF, ON, any FlexLogic operand
Default: OFF
Select the FlexLogic operand for the trigger. When it transitions from Off to On, it opens the page specified by the
ACTIVATE PAGE
setting. The FlexLogic operands selectable depend on product. Select it from the drop-down list. Or click
or select the field and start typing to auto-fill. For example, typing F displays FIRST ETHERNET FAIL, while typing BR
displays the first breaker option.
ACTIVATE PAGE
Range: Product Information, SLD 1…5, Annunciator, Annunciator 1…8, Actual Values Phasors 1…6, Tabular 1…5, Event
Records, Targets
Default: Product Information
This setting specifies the page to display on the graphical front panel when the FlexLogic operand selected by its
CONDITON
setting transitions from Off to On.
The "Annunciator" option without a page number specifies the first annunciator page in the following sequence:
–
The first annunciator page that contains an annunciator window that is in alarm (fast flash)
–
The first annunciator page that contains an annunciator window that is in ringback. Ringback is a "return alert."
Visual and audible signals are given when conditions return to normal, then the sequence returns to normal by
pushing the
RESET
button.
–
The first annunciator page that contains an annunciator window that is in abnormal state
–
Annunciator page 1
The Tabular option displays a configured actual values/metering page.
The Targets option displays error messages, such as wrong transceiver, similar to event record entries.
5.3.4 Clear relay records
SETTINGS
PRODUCT SETUP
CLEAR RELAY RECORDS
CLEAR RELAY
RECORDS
CLEAR FAULT REPORTS:
Off
Range: FlexLogic operand
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...