5-220
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
Figure 5-115: Applications of the PH DIST XFMR VOL/CUR CONNECTION settings
PHS DIST Z1 REACH
— This setting defines the zone reach for the forward and reverse applications. In the non-directional
applications, this setting defines the forward reach of the zone. The reverse reach impedance in non-directional
applications is set independently. The reach impedance is entered in secondary ohms. The reach impedance angle is
entered as the
PHS DIST Z1 RCA
setting.
To achieve specified operating speed of distance elements, the relay internally calculates source to line impedance ratio
(SIR) from fault phasors. In these calculations, line impedance is estimated based on the zone 1 reach setting. Therefore, in
order to calculate the SIR value properly and to maintain the optimal operating speed of the distance elements, set zone 1
reach with a regular 80 to 85% of the line impedance reach setting, even when zone 1 is disabled.
PHS DIST Z1 RCA
— This setting specifies the characteristic angle (similar to the "maximum torque angle" in previous
technologies) of the phase distance characteristic for the forward and reverse applications. In the non-directional
applications, this setting defines the angle of the forward reach impedance. The reverse reach impedance in the non-
directional applications is set independently. The setting is an angle of reach impedance as shown in the distance
characteristic figures earlier. This setting is independent from
PHS DIST Z1 DIR RCA
, the characteristic angle of an extra
directional supervising function.
PHS DIST Z1 REV REACH
— This setting defines the reverse reach of the non-directional zone (
PHS DIST Z1 DIR
setting). The
value must be entered in secondary ohms. This setting does not apply when the zone direction is set to "Forward" or
"Reverse."
PHS DIST Z1 REV REACH RCA
— This setting defines the angle of the reverse reach impedance of the non-directional zone
(
PHS DIST Z1 DIR
setting). This setting does not apply when the zone direction is set to "Forward" or "Reverse."
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...