CHAPTER 5: SETTINGS
CONTROL ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-331
5
breaker restrike condition is declared in the corresponding phase and the
BRK RESTRIKE 1 OP
operand asserts for a short
period of time. The user can add counters and other logic to facilitate the decision making process as to the appropriate
actions upon detecting a single restrike or a series of consecutive restrikes.
A restrike event (FlexLogic operand) is declared if all of the following hold:
•
The current is initially interrupted
•
The breaker status is open
•
An elevated high frequency current condition occurs (if the
BREAKER RESTRIKE 1 HF DETECT
setting is Enabled, otherwise
the condition is bypassed), and
•
The current subsequently drops out again
The algorithm is illustrated in the following state machine diagram.
Figure 5-189: Algorithm illustration of state machine to detect restrike
In this way, a distinction is made between a self-extinguishing restrike and permanent breaker failure condition. The latter
can be detected by the breaker failure function or a regular instantaneous overcurrent element. Also, a fast succession of
restrikes is picked up by breaker failure or instantaneous overcurrent protection.
The following settings are available for each element.
BREAKER RESTRIKE 1 FUNCTION
— Enables and disables operation of the breaker restrike detection element.
BRK RSTR 1 BLOCK
— Blocks operation of the breaker restrike detection element.
BREAKER RESTRIKE 1 SOURCE
— Selects the source of the current for this element. This source must have a valid CT bank
assigned.
BREAKER RESTRIKE 1 PICKUP
— Specifies the pickup level of the overcurrent detector in per-unit values of CT nominal
current.
BREAKER RESTRIKE 1 RESET DELAY
— Specifies the reset delay for this element. When set to “0 ms,” then FlexLogic operand is
picked up for only 1/8th of the power cycle.
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...