CHAPTER 5: SETTINGS
GROUPED ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-221
5
PHS DIST Z1 COMP LIMIT
— This setting specifies the shape the operating characteristic. In particular, it produces the lens-
type characteristic of the mho function and a tent-shaped characteristic of the reactance boundary of the quadrilateral
function. If the mho shape is selected, the same limit angle applies to both the mho and supervising reactance
comparators. In conjunction with the mho shape selection, the setting improves loadability of the protected line. In
conjunction with the quadrilateral characteristic, this setting improves security for faults close to the reach point by
adjusting the reactance boundary into a tent-shape.
PHS DIST Z1 DIR RCA
— This setting selects the characteristic angle (or maximum torque angle) of the directional supervising
function. If the mho shape is applied, the directional function is an extra supervising function as the dynamic mho
characteristic is itself directional. In conjunction with the quadrilateral shape, this setting defines the only directional
function built into the phase distance element. The directional function uses the memory voltage for polarization. This
setting typically equals the distance characteristic angle
PHS DIST Z1 RCA
.
PHS DIST Z1 DIR COMP LIMIT
— Selects the comparator limit angle for the directional supervising function.
PHS DIST Z1 QUAD RGT BLD
— This setting defines the right blinder position of the quadrilateral characteristic along the
resistive axis of the impedance plane (see the Quadrilateral Phase Distance Characteristic figures). The angular position of
the blinder is adjustable with the use of the
PHS DIST Z1 QUAD RGT BLD RCA
setting. This setting applies only to the
quadrilateral characteristic and is set giving consideration to the maximum load current and required resistive coverage.
PHS DIST Z1 QUAD RGT BLD RCA
— This setting defines the angular position of the right blinder of the quadrilateral
characteristic (see the Quadrilateral Distance Characteristic figures).
PHS DIST Z1 QUAD LFT BLD
— This setting defines the left blinder position of the quadrilateral characteristic along the
resistive axis of the impedance plane (see the Quadrilateral Distance Characteristic figures). The angular position of the
blinder is adjustable with the use of the
PHS DIST Z1 QUAD LFT BLD RCA
setting. This setting applies only to the quadrilateral
characteristic and is set with consideration to the maximum load current.
PHS DIST Z1 QUAD LFT BLD RCA
— This setting defines the angular position of the left blinder of the quadrilateral
characteristic (see the Quadrilateral Distance Characteristic figures).
PHS DIST Z1 SUPV
— The phase distance elements are supervised by the magnitude of the line-to-line current (fault loop
current used for the distance calculations). For convenience,
is accommodated by the pickup (that is, before being
used, the entered value of the threshold setting is multiplied by ).
If the minimum fault current level is sufficient, set the current supervision pickup above maximum full load current
preventing maloperation under VT fuse fail conditions. This requirement can be difficult to meet for remote faults at the
end of zones 2 and above. If this is the case, set the current supervision pickup below the full load current, but this can
result in maloperation during fuse fail conditions.
PHS DIST Z1 VOLT LEVEL
— This setting is relevant for applications on series-compensated lines, or in general, if series
capacitors are located between the relaying point and a point where the zone does not overreach. For plain (non-
compensated) lines, set to zero. Otherwise, the setting is entered in per unit of the phase VT bank configured under the
DISTANCE SOURCE
. Effectively, this setting facilitates dynamic current-based reach reduction. In non-directional
applications (
PHS DIST Z1 DIR
set to “Non-directional”), this setting applies only to the forward reach of the non-directional
zone. See the Application of Settings chapter for information on calculating this setting for series compensated lines.
PHS DIST Z1 DELAY
— This setting allows the user to delay operation of the distance elements and implement stepped
distance protection. The distance element timers for zones 2 and higher apply a short dropout delay to cope with faults
located close to the zone boundary when small oscillations in the voltages or currents can inadvertently reset the timer.
Zone 1 does not need any drop-out delay since it is sealed-in by the presence of current.
PHS DIST Z1 BLK
— This setting enables the user to select a FlexLogic operand to block a given distance element. VT fuse fail
detection is one of the applications for this setting.
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...