5-62
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
Figure 5-21: Default IEC 61850 Logical Devices panel with devices middle and nodes right
To configure logical devices and nodes:
1.
Right-click an entry and edit an existing device, add a new one, or move a logical node. The rest of this section
explains the window and how to perform these actions.
The default logical device categories are as follows:
•
Master
— Communications, including GOOSE, reports, Remote I/O, Virtual Inputs, Modbus, DNP, and setting group
control
•
System
— Power system devices: breakers, switches, CTs, VTs, and so on, including interfaces to these, such as AC
inputs, contact I/O, transducer I/O, HardFiber I/O
•
Prot
— Protection and protection-related functions
•
Ctrl
— Control and monitoring functions
•
Meter
— Metering and measurement functions
•
Gen
— FlexLogic, Virtual Outputs, non-volatile latches, FlexElements, recording (for example oscillography), security,
front panel, clock
For the Master logical device, the following logical nodes have fixed assignment:
•
The LLN0 in the Master logical device, which includes setting group, GOOSE and report control blocks, and datasets
•
LPHD1 — Models common issues for physical devices
•
GGIO1 — For unmapped FlexLogic operands
•
GGIO2 — For Virtual Input control
•
GGIO3 — For RxGOOSE Inputs
•
GGIO4 — For unmapped FlexAnalog operands
•
LGOS logical nodes — For GOOSE subscription
The Logical Devices panel has middle and right panes. The middle pane has a list of the instantiated logical devices in the
sequence that they appear in SCL, with one device selected. The right pane has a list of the logical nodes presently
assigned to the selected logical device in lexicographic order by logical node name.
In the middle pane logical devices are shown with their product-related name, followed in brackets by their function-
related ldName, and followed by the value of their confRev. In the following example, by right-clicking and editing, the
Protection logical device has been set to instance name "Prot", the function-related name "Feeder1Prot" and the
configuration revision "2016-03-07 08:46." The text is clipped on the right if the line is longer than the available width. The
next paragraphs explain how to do this setup.
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...