9-40
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
SINGLE-POLE TRIPPING
CHAPTER 9: THEORY OF OPERATION
9
Figure 9-29: Phase selection principle (ABC phase rotation)
Due to dual comparisons, the algorithm is very secure. For increased accuracy and to facilitate operation in weak systems,
the pre-fault components are removed from the analyzed currents. The algorithm is very fast and ensures proper phase
selection before any of the correctly set protection elements operates.
Under unusual circumstances, such as weak-infeed conditions with the zero-sequence current dominating during any
ground fault, or during cross-country faults, the current-based phase selector may not recognize any of the known fault
pattern. If this is the case, voltages are used for phase selection. The voltage algorithm is the same as the current-based
algorithm. For example, phase angles between the zero-sequence, negative-sequence, and positive-sequence voltages
are used. The pre-fault values are subtracted prior to any calculations.
The pre-fault quantities are captured and the calculations start when the disturbance detector (50DD) operates. When an
open pole is declared, the phase selector resets all its outputs operands and ignores any subsequent operations of the
disturbance detector.
The phase selector runs continuously. When there is no disturbance in the power system, and the disturbance detector
(50DD) from the source assigned as the
DISTANCE SOURCE
is reset, then the
PHASE SELECT VOID
FlexLogic operand is set and
all other phase selector operands are reset. All current and voltage sequence components are memorized and
continuously updated.
When the disturbance detector (50DD) operates, memory stops being updated and retains two cycles of old current and
voltage values. First, purely fault components of current and voltage are calculated by removing the pre-fault (memory)
quantities from presently calculated values. A series of conditions are checked with respect to magnitudes and phase
angles of current and voltage symmetrical components in order to detect the fault type. Secondly, currents are used to
identify the fault type (AG, BG, CG, AB, BC, CA, ABG, BCG, or CAG) according to the Phase Selection Principle figure. If the
currents fail to identify the fault type, and voltages are available, then voltages are used. If any of the above types is
determined, then the corresponding FlexLogic operand outlined in the following table is asserted.
Table 9-2: FlexLogic operands asserted
Operand
Description
PHASE SELECT AG
Asserted when a phase A to ground fault is detected
PHASE SELECT BG
Asserted when a phase B to ground fault is detected
PHASE SELECT CG
Asserted when a phase C to ground fault is detected
PHASE SELECT AB
Asserted when a phase A to B fault is detected
PHASE SELECT BC
Asserted when a phase B to C fault is detected
PHASE SELECT CA
Asserted when a phase C to A fault is detected
PHASE SELECT ABG
Asserted when a phase A to B to ground fault is detected
PHASE SELECT BCG
Asserted when a phase B to C to ground fault is detected
PHASE SELECT CAG
Asserted when a phase C to A to ground fault is detected
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...