5-336
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
The open pole detector is intended to identify an open pole of the line circuit breaker. The scheme monitors the breakers
auxiliary contacts, current in the circuit, and optionally voltage on the line. The scheme generates output operands used to
block the phase selector and some specific protection elements, thus preventing maloperation during the dead time of a
single-pole autoreclose cycle or any other open pole conditions.
The scheme declares an open pole at the moment a single-pole trip is issued.
In two-breaker and breaker-and-a-half applications, an open pole condition is declared when one or more of the following
hold:
•
Both breakers have an open pole on the same phase
•
The current on the line drops below a threshold
•
The current and voltage on the line drop below a threshold
The open pole feature uses signals defined by the
GROUPED ELEMENTS
SETTING GROUP 1(6)
DISTANCE
DISTANCE
SOURCE
setting. Voltage supervision can be used only with wye VTs on the line side of the breaker.
OPEN POLE CURRENT PICKUP
— This setting establishes the current threshold below which an open pole is declared.
OPEN POLE LINE XC1
— Specifies positive-sequence reactance of the entire line. If shunt reactors are applied, this value is a
net capacitive reactance of the line and the reactors installed between the line breakers. The value is entered in secondary
ohms. This setting is relevant if open pole condition at the remote end of the line is to be sensed and utilized by the relay.
OPEN POLE LINE XC0
— Specifies zero-sequence reactance of the entire line. If shunt reactors are applied, this value is a net
capacitive reactance of the line and the reactors installed between the line breakers. Do not enter the value in secondary
ohms. This setting is relevant if open pole condition at the remote end of the line is to be sensed and utilized by the relay
(
OPEN POLE REM OP
FlexLogic operand).
OPEN POLE REM CURR PKP
— Specifies pickup level for the remote-end current estimated by the relay as the local current
compensated by the calculated charging current. The latter is calculated based on the local voltages and the capacitive
reactances of the line. This setting is relevant if open pole condition at the remote end of the line is to be sensed and
utilized by the relay (
OPEN POLE REM OP
FlexLogic operand).
OPEN POLE MODE
— Selects the mode of operation of the open pole function. When the “Accelerated” mode is chosen, an
open pole is declared ½ cycle after trip output operation and before the breaker pole opens. This blocks distance loops
involved in the faulted phase and phase selector, and arms the trip output to produce three-pole trip for the next fault. If
the fault evolves into multi-phase fault before breaker pole opens for the first fault, the remaining in-service distance loops
initiates a three-pole trip. When the “Traditional” mode is selected, then an open pole is declared only after the breaker
opens and current disappears. If the fault evolves into a multi-phase fault before the circuit breaker pole opens for the first
fault, the phase selector changes the fault type from a single-line-to-ground fault to a multi-phase fault, thereby initiating
a three-pole trip.
OPEN POLE CURRENT
PKP: 0.050 pu
Range: 0.020 to 30.000 pu in steps of 0.001
OPEN POLE LINE XC1:
9999.9
Ω
Range: 300.0 to 9999.9 ohms in steps of 0.001
OPEN POLE LINE XC0:
9999.9
Ω
Range: 300.0 to 9999.9 ohms in steps of 0.001
OPEN POLE REM CURR
PKP: 0.050 pu
Range: 0.020 to 30.000 pu in steps of 0.001
OPEN POLE MODE:
Accelerated
Range: Accelerated, Traditional
OPEN POLE DETECTION:
I AND V AND CBaux
Range: I AND V AND CBaux, I AND V only
OPEN POLE TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
OPEN POLE EVENTS:
Disabled
Range: Enabled, Disabled
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...