CHAPTER 5: SETTINGS
CONTROL ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-333
5
The CT failure function detects problems with system current transformers used to supply current to the relay. This logic
detects the presence of a zero-sequence current at the supervised source of current without a simultaneous zero-
sequence current at another source, zero-sequence voltage, or some protection element condition.
The CT failure logic (see later) is based on the presence of the zero-sequence current in the supervised CT source and the
absence of one of three or all of the three following conditions:
•
Zero-sequence current at different source current (can be different set of CTs or different CT core of the same CT)
•
Zero-sequence voltage at the assigned source
•
Appropriate protection element or remote signal
Settings are described as follows.
CT FAIL 1 FUNCTION
— Enables or disables operation of the CT failure element.
CT FAIL 1 BLOCK
— Selects a FlexLogic operand to block operation of the element during some condition (for example, an
open pole in process of the single pole tripping-reclosing). Local signals or remote signals representing operation of some
remote current protection elements via communication channels can also be chosen.
CT FAIL 1 3I0 INPUT 1
— Selects the current source for input 1. The most critical protection element should also be assigned
to the same source.
CT FAIL 1 3I0 INPUT 1 PICKUP
— Selects the 3I_0 pickup value for input 1 (the main supervised CT source).
CT FAIL 1 3I0 INPUT 2
— Selects the current source for input 2. Input 2 should use a different set of CTs or a different CT core
of the same CT. If 3I_0 does not exist at source 2, then a CT failure is declared.
CT FAIL 1 3I0 INPUT 2 PICKUP
— Selects the 3I_0 pickup value for input 2 (different CT input) of the relay.
CT FAIL 1 3V0 INPUT
— Selects the voltage source.
CT FAIL 1 3V0 INPUT PICKUP
— Specifies the pickup value for the 3V_0 source.
CT FAIL 1 PICKUP DELAY
— Specifies the pickup delay of the CT failure element.
CT FAIL 1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
CT FAIL 1 EVENTS:
Disabled
Range: Disabled, Enabled
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...