5-124
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
See the figure in the Setting Groups section of the Control Elements section later in this chapter for an example of group
activation.
5.3.12.6 Event cause LED 1(9)
SETTINGS
PRODUCT SETUP
USER-PROGRAMMABLE LEDS
EVENT CAUSE LED 1(9)
For the graphical front panel, the event cause LED settings select the FlexLogic operands that control the LEDs.
LED 1 TYPE
— If set to "Self-Reset," the LED illumination tracks the state of the selected LED operand. If set to "Latched," the
LED, once lit, remains so even the LED operand state already de-asserts, until reset by the front panel
RESET
button, from a
remote device via a communications channel, or from any programmed operand.
The table outlines default input operand and output operands for each event cause LED.
Table 5-17: Default input and output operand for event cause LEDs
5.3.13 User-programmable self-tests
SETTINGS
PRODUCT SETUP
USER-PROGRAMMALBE SELF TESTS
EVENT CAUSE LED 1
LED 1 OPERAND:
LED PICKUP
Range: FlexLogic operand
LED 1 COLOR:
Green
Range: Red, Green, Orange
LED 1 TYPE:
Self-Reset
Range: Self-Reset, Latched
LED
Default input operand
Output operand
Default color
Event Cause LED 1
LED PICKUP
EVENT CAUSE LED 1
Green
Event Cause LED 2
LED VOLTAGE
EVENT CAUSE LED 2
Orange
Event Cause LED 3
LED CURRENT
EVENT CAUSE LED 3
Orange
Event Cause LED 4
LED FREQUENCY
EVENT CAUSE LED 4
Orange
Event Cause LED 5
LED OTHER
EVENT CAUSE LED 5
Orange
Event Cause LED 6
LED PHASE A
EVENT CAUSE LED 6
Orange
Event Cause LED 7
LED PHASE B
EVENT CAUSE LED 7
Orange
Event Cause LED 8
LED PHASE C
EVENT CAUSE LED 8
Orange
Event Cause LED 9
LED NEUTRAL/GROUND
EVENT CAUSE LED 9
Orange
USER-PROGRAMMABLE
SELF TESTS
DIRECT RING BREAK
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
DIRECT DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped
with Direct Input/Output module.
RxGOOSE OFF
FUNCTION: Enabled
Range: Disabled, Enabled
FIRST ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
SEC. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
THIRD ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
SFP MODULE FAIL
FUNCTION: Disabled
Range: Disabled, Enabled
BATTERY FAIL
FUNCTION: Enabled
Range: Disabled, Enabled
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...